Installation and

Operating Instructions

for 

STERIFLO

®

Ultra Violet

Water Treatment System

Models SF1000S mkII & SF2500S mkII

Please pass these instructions onto the operator

of this equipment.

Distributed in Australia by Davey Water Products Pty Ltd.

DO NOT DISASSEMBLE ANY COMPONENTS UNTIL YOU HAVE FULLY READ
THESE INSTRUCTIONS!

Ultra violet radiation is harmful to skin & eyes.
DO NOT LOOK AT UV LAMP WHILE LAMP IS OPERATING.

WARNING: The UV Chamber operates under pressure.  Under no
circumstances should the UV Chamber be disassembled unless the internal
pressure of the unit has been relieved.  Failure to observe this warning will
expose persons to the possibility of personal injury and may result in
damage to the UV system or other property.

This unit is designed to treat water at ambient temperatures (5

o

C to 45

o

C).

Contact your dealer for details of UV systems suitable for hot water service.

Maximum operating pressure for stainless steel UV chambers is 850kPa (125
psi).  If this pressure can be exceeded or if operating close to this pressure
fit a suitable pressure limiting valve in the supply to the UV chamber.

Plastic UV chambers have a maximum operating pressure of 400kPa (60 psi).

Содержание STERIFLO SF1000S mkII

Страница 1: ...should the UV Chamber be disassembled unless the internal pressure of the unit has been relieved Failure to observe this warning will expose persons to the possibility of personal injury and may resul...

Страница 2: ...Connection Page 5 Electrical Power Surge Protection Page 5 6 Pipe Connections Page 6 Pre treatment drinking water Page 6 Lamp Installation Page 7 Operation Page 7 Maintenance Page 8 9 Water Quality Pa...

Страница 3: ...with mounting brackets Before installing your new Steriflo please read all instructions carefully as failures caused by incorrect installation or operation are not covered by the guarantee Your Ultra...

Страница 4: ...Steriflo system from the weather make sure the site is water proof frost free and has adequate ventilation The unit should be either horizontally mounted with the inlet and outlet facing upwards or v...

Страница 5: ...or light mounted on its front panel adjacent to the amber power on LED This light will be illuminated whenever the Steriflo control box senses no lamp current There is also an audible alarm in the eve...

Страница 6: ...90o bends of a suitable material are connected to the inlet and outlet of the chamber Larger diameter pipe may be used to minimise resistance to flow but maximum flow rates should not be exceeded as c...

Страница 7: ...ansport tube touching the lamp as little as possible Handle the lamp by the ends where possible Wipe with clean cloth and methylated spirits if fingerprints or dirt need removing Slide the lamp into t...

Страница 8: ...it clean The sleeve should be cleaned every three months or as required Sleeve removal use care fragile 1 Remove lamp as described 2 Remove drain port cap and empty water from chamber 3 Undo nut at o...

Страница 9: ...und and the red LED will light and the alarm contacts will changeover These are able to close a normally open solenoid valve The alarm function can be checked by switching the unit off disconnecting t...

Страница 10: ...3N70 2 per sleeve d Lamp Connector All models S114 2 WARNING When servicing or attending your Steriflo always ensure power is switched off and lead unplugged Electrical connections should be serviced...

Страница 11: ...hours later Severe exposure sore red eyes sensitive to light painful to keep eyes open SKIN Mild exposure slight reddening tenderness mild sunburn symptoms Severe exposure skin sloughing peeling weep...

Страница 12: ...ustralian states or the Consumers Guarantee Act 1993 NZ Davey shall not be liable for any loss of profits or any consequential indirect or special loss damage or injury of any kind whatsoever arising...