Power Module Specification
2.1
GFPS-0202
Technical Specification
Rated Input Voltage
100~240 VAC (rated)
Inrush Current (Cold Start)
34 A
Rated Power
48 W
/
2 A
Output Voltage
24 VDC ± 1%
Overload Protection
Hiccup Mode
Overload
120% - 185% Rated Output Power
Overvoltage Protection
Clamper Overvoltage Protection
Overvoltage
30-34 VDC
General Specification
Dimension (W*D*H)
20 x 100 x 96mm
Weight
126g
Ambient Temperature (Operation)
-
20℃...+60℃
Ambient Humidity
RH 20%...90%
Altitude Limit
< 2000 m
Ingress Protection (IP)
IP 20
Pollution Severity
II
Safety Approval
CE
Wiring Range (IEC / UL)
0.2 mm²~2.5 mm² / AWG 26~12
Wiring Ferrules
DN00508D
、
DN00708D
、
DN01508D