background image

2 of 2

Setting the Slave ID and Read 

Registers.

1.  The Slave ID on the DAT3016 is 1.

2.  The Register of Channel 0 is 40015. 

3.  As the DAT3016 is a 4 channel thermocouple 

Modbus Slave we would like to read all 4 chan-

nels, so we type 4 in No. of Regs.

4.  The offset is 40001.

More information on the register tables are in the 

User Guide.

Sending the Command and 

Receiving the Temperature.

1.  Click Send.

2.  If all is good the DAT3016 should return the 

Temperature.

3.  The result is a temperature of 254 which equals 

25.4’C. 