background image

FEATURES
Input for E, J, K, N, S, R, B e T thermocouple type
Two wire 4÷20 mA voltage linear output
Zero and span programmable by DIP SWITCH
Good accuracy and performance stability
Programmable for both°C & °F  scales
One model covers both K & J TC type.
Conform to EMC standards -  CE mark
Suitable for mounting on DIN B connection heads
Low profile
Low cost

APPLICATIONS
Temperature monitoring and controlling in:
- Process controls
- Automation systems
- Energy sources management

 GENERAL INFORMATION

The two wire DAT1112 transmitter has been designed to give an output current signal of 4÷20 mA; this signal is perfectly linear and
proportional to the voltage generated by  the thermocouple sensor connected to its input. The output current signal is supplied on the
same two wires used to power the device.
The user  can program the full scale easily and quickly by means of four way  DIP switch. The "zero" value can be varied between
 -50°C to +50°C or -100 to +100 °F and the span value can be programmed following TC limits only.Moreover  the same model is suitable
for K and J thermocouple, so as another model is suitable for R and S thermocouple.  The maximum accuracy and reliability are ensured
for all the functions (conditioning, cold junction compensation and current transmission) thanks to the employement  of  high precision
and high-quality components and to the use of the SMD technology. The device, conform to the 89/336/EEC directives on
electromagnetic compatibility, is housed in a  rugged self-extinguishing  plastic case suitable for  direct  mounting on the connection head.

TECHNICAL SPECIFICATIONS  (Typical @ 25°C and in the nominal conditions)

Input
Type of sensor

TC type K, J, S, N, E, T, B and R according to SIPT68

Zero

Programmable in the -50°C to +50°C range or -100°F to 100°F range.

Span

Programmable according to the "version table".

Influence of line resistance

0,2 µV / 

Output
Sensor interruption signaling

Positive out of scale (< 3.5 mA on request)

Measuring current

4÷20 mA, two wires

Current limitation

about 35 mA

Protection against polarity reversal

60 V reverse max

Response time ( 10 to 90% of full scale)

0.3 s.

Warm-up time

3 minutes

Performances
Calibration inaccuracy

± 0.1% of f.s. or ± 0.2°C

Linearity error (inclusive of hysteresis and supply

± 0.1% of full scale

                                voltage variations)
Electromagnetic Compatibility (EMC)

According to EN50081-2 and EN50082-2

Thermal drift

0.02% of full scale/°C ( for span >= 300 °C / 500 °F )

Power supply voltage

12 ÷ 32 V

Operating temperature

- 20 ÷ 70 °C

Storage temperature

- 40 ÷ 100 °C

Relative humidity (non-condensing)

0 ÷ 90 %

Weight

25 grams

DAT 1112

Programmable range transmitter

for thermocouple

Содержание DAT1112

Страница 1: ...ns conditioning cold junction compensation and current transmission thanks to the employement of high precision and high quality components and to the use of the SMD technology The device conform to the 89 336 EEC directives on electromagnetic compatibility is housed in a rugged self extinguishing plastic case suitable for direct mounting on the connection head TECHNICAL SPECIFICATIONS Typical 25 ...

Страница 2: ...he device is programmed the calibration is carried out by adjusting the zero and the span potentiometer as follows apply a signal corresponding to desired minimum input signal and than adjust the zero potentiometer to get Iout 4 00 mA Apply a signal corresponding to desired maximum input signal and than adjust the span potentiometer to get Iout 20 00 mA Repeat these operations until the needed acc...

Страница 3: ...ERO PROGRAMMING SPAN PROGRAMMING Range SW4 SW2 It is not necessary because the transmitter is able to operate either with the thermocouple R or the thermocouple S It is not necessary Zero could be adjusted from 50 C up to 50 C by the appositely dedicated ZERO adjusting potentiometer It is not necessary Zero could be adjusted from 50 C up to 50 C by the appositely dedicated ZERO adjusting potentiom...

Страница 4: ...he dei propri prodotti senza alcun preavviso Datexel reserves its right to modify the characteristics of its products totally or in part without warning at any time Version 5 thermocouple N SPAN PROGRAMMING Sensor Range SW4 SW2 150 C to 200 C ON OFF 200 C to 480 C ON ON 480 C to 580 C OFF OFF N 580 C to 1300 C OFF ON ZERO PROGRAMMING Sensor Range SW3 SW1 N 50 C to 15 C 15 C to 50 C OFF ON OFF OFF ...

Отзывы: