CALIBRATION

The  procedure  of  calibration  is  performed  in  factory  on  all  the  modules  during  the  testing  phase.  However  it  can  be  convenient  to  make  another 
calibration of the module according to the requirements of the user. To make this, it is necessary to use precision instruments and to correctly perform 
all the necessary steps, because any error reduces the accuracy and the good operation of the device.

To re-calibrate the device, follow this procedure:
1 – Turn on the device in INIT condition
2 – Connect a calibrator to the channel #0.
3 – Program the input type to be calibrated
4 – Set the calibrator at 0V or 0mA
5 – Write on the “Test” register (40001) the value 20.
6 – Set the calibrator to the full-scale value (10V or 20mA)
7 – Write on the “Test” register (40001) the value 30.
8 – Repeat point 3 to 7 for each input type to be calibrated.

PROCEDURES

HOW TO USE THE “INIT” FUNCTION

If the exact configuration of a module is unknown, it can result impossible to establish a communication with it.
The “INIT” function gives a solution to this throuble:

- Connect to the RS485 net only the device to configure.
- Turn off the device.
- Connect the INIT pin (D) to the GND pin (C).
- Turn on the device.
- Ensures that the “PWR” green LED on the front of the enclosure is lighted.

If not, control the voltage supply connections ( I and J pins ) and RS485 net connections ( A and B pins).

 If the supply connection is right, and the led still unlighted, it can be necessary to invert the RS485 pins connection.

- Set the communication port to these values:

baud-rate = 9600 bps
parity = None
n° bits = 8 
stop bits = 1

- The device now communicates at the address 01 with the RTU protocol.
- Read or program the desired settings on the registers:

40006 : “Communication” for the baud-rate setting
40007 : “Address” for the net address of the device

- Turn off the device.
- Disconnect the INIT pin from the GND pin.
- Turn on the device.
- Set the communication port at the baud-rate programmed in the 40006 register.
- The device now communicates with the addressprogrammed in the 40007 register.

NOTE

: The default manufacturer programmation is the following:

- Address : 01
- Baud-rate : 38400 bps
- Protocol : RTU

WATCHDOG

The modules has been provided of a Host Watchdog timer which, when it is enabled, makes to start the alarm each time the communication between 
the  module  and  the  host  is  inactive  for  a  period  time  greater  then  the  programmed  one.  When  the  alarm  goes  on,  the  values  of  the  outputs  are 
automatically  converted  to  the  values  set  as  ‘safety  value’,  that  corresponding  to  the  state  in  which  the  outputs  must  be  putted,  and  therefore  the 
actuators  are  putted,  to  avoid  damages  to  the  system  in  case  of  failure.  Moreover,  under  the  alarm  condition  the  green  LED  on  the  front  of  the 
enclosure is blinking and the “Watchdog Event” coil is forced to 1.
To return from the alarm condition, reset the coil “Watchdog Event” coil: the LED stop blinking and it is possible to set the outputs.
There is also a Module Watchdog timer that monitor the internal CPU work and is active when the CPU don't function correctly for any reason, and 
resets the module. After the reset, all outputs will assume their initial default value (“power up value”), that may be different to the output value after the 
reset.

SYNCHRONISM

The Synchronism function is performed by a command sent to all devices connected on the net. When the devices receive the Sync command, all 
input states are saved in the relative register, to be read after time. Doing this, it is possible to read the value of all inputs at the Sync command time.
To send the synchronism command, write the value 10 in the “Test” register (40001) at the address 255.
NOTE: The sync values are not saved in EPROM.

Содержание DAT 3015-I

Страница 1: ...oils bits 3xxxx and 4xxxx Registers words PRELIMINAR DESCRIPTION Register 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021 40022 40023 40024 40025 40026 40027 40028 40029 40030 Description Test Firmware Version Device Name Communication Address RX TX Delay Watchdog Timer Coils reserved Channel Enable reserved reserved Inp...

Страница 2: ...ATION Set the bits of this register as shown in the following table to set the baud rate the bit number the parity type and the protocol type Manufacturer default 38400 bps RTU mode 40007 ADDRESS Specify the net address of the device there are allowed the address from 1 to 255 Each device connected to the same net must have a unique address The address 255 is used for broadcast functions i e synch...

Страница 3: ...ny command for a time longer than the time specified in the 40009 register the WatchDog alarm Event coil is forced to 1 see the Procedures section 0 Watchdog alarm disabled 1 Watchdog alarm enabled 00010 WATCHDOG ALARM EVENT This coil indicates the condition of WatchDog Alarm If the alarm is enabled and the device does not receive any command for a time longer than the time specified in the 40009 ...

Страница 4: ...he desired settings on the registers 40006 Communication for the baud rate setting 40007 Address for the net address of the device Turn off the device Disconnect the INIT pin from the GND pin Turn on the device Set the communication port at the baud rate programmed in the 40006 register The device now communicates with the addressprogrammed in the 40007 register NOTE The default manufacturer progr...

Отзывы: