background image

Current

 Input to RS485 MODBUS  

Phone: +1 561 779 5660 E-mail : [email protected] - Web Site www.datexel.com

 

 

DAT 3015-V

DAT 3015-V

DAT 3015- I

DAT 3015- I

pag 1/4

Coil

00009
00010
00011

Description

Watchdog Enable
Watchdog Event
Power Up Event

Access

R/W
R/W
R/W

E

2

P

Distributed I/O device

4 channels V or mA inputs

on RS-485 network

User Guide – MODBUS protocol

User Guide – MODBUS protocol

Firmware Version : 3310

Firmware Version : 3310

All the data variables shared by a Modbus module are shown in tables, where each data is linked to one address.
Each data can be of two types:

- “COIL”, composed by a single bit, can be associated to digital input (switch), digital outputs (relays), logic states (alarms).

- “REGISTER”, composed by 2 bytes (16 bits), can be associated to analog input or outputs, variables, set-point, etc...

A register can also include the image of more coils, for example the 16 digital inputs of a device can be read and write as bit, one by one, addressing 
the relative coil , or they can be read or write as a single 16-bit port addressing the associated register, where for example the last significant bit will 
respond to the first coil.

In the Modbus protocol, coils and registers are divided in banks:
0xxxx and 1xxxx = Coils (bits)
3xxxx and 4xxxx = Registers (words)

PRELIMINAR DESCRIPTION

Register

40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
40021
40022
40023
40024
40025
40026
40027
40028
40029
40030

Description

Test
Firmware Version

Device Name

Communication
Address
RX/TX Delay
Watchdog Timer
Coils
-- (reserved)
Channel Enable
-- (reserved)
-- (reserved)
Input # 0
Input # 1
Input # 2
Input # 3
-- (reserved)
-- (reserved)
-- (reserved)
-- (reserved)
Sync. value input # 0
Sync. value input # 1
Sync. value input # 2
Sync. value input # 3
-- (reserved)
-- (reserved)
-- (reserved)
-- (reserved)

Access

R/W

R
R

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

E

2

P

*
*
*
*
*
*

*
*
*

REGISTERS TABLE

NOTE:

The  registers  marked  with  '  *  '  in  the  '  E

2

P  '  column  are  saved  in 

EEPROM each time they are written, to be automatically reloaded 
to each power-on of the device.

COILS TABLE

Function

01
02
03
04
05
06
15
16
08

Description

Read multiple coils (0xxxx bank)
Read multiple coils (1xxxx bank)
Read multiple registers (4xxxx bank)
Read multiple registers (3xxxx bank)
Write single coil
Write single register
Write multiple coils
Write multiple registers
Diagnostic

IMPLEMENTED MODBUS FUNCTIONS

NOTE:

For  DAT3000  series  devices,  the  bank  0xxxx  is  a  mirror  of  bank 
1xxxx,  as  the  3xxxx  bank  is  a  mirror  of  bank  4xxxx, as  for  i.e.  the 
first  register  can  be  read  indifferently  as  30001  (with  the  function 
04) or 40001 (with the function 03)

Содержание DAT 3015-I

Страница 1: ...oils bits 3xxxx and 4xxxx Registers words PRELIMINAR DESCRIPTION Register 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021 40022 40023 40024 40025 40026 40027 40028 40029 40030 Description Test Firmware Version Device Name Communication Address RX TX Delay Watchdog Timer Coils reserved Channel Enable reserved reserved Inp...

Страница 2: ...ATION Set the bits of this register as shown in the following table to set the baud rate the bit number the parity type and the protocol type Manufacturer default 38400 bps RTU mode 40007 ADDRESS Specify the net address of the device there are allowed the address from 1 to 255 Each device connected to the same net must have a unique address The address 255 is used for broadcast functions i e synch...

Страница 3: ...ny command for a time longer than the time specified in the 40009 register the WatchDog alarm Event coil is forced to 1 see the Procedures section 0 Watchdog alarm disabled 1 Watchdog alarm enabled 00010 WATCHDOG ALARM EVENT This coil indicates the condition of WatchDog Alarm If the alarm is enabled and the device does not receive any command for a time longer than the time specified in the 40009 ...

Страница 4: ...he desired settings on the registers 40006 Communication for the baud rate setting 40007 Address for the net address of the device Turn off the device Disconnect the INIT pin from the GND pin Turn on the device Set the communication port at the baud rate programmed in the 40006 register The device now communicates with the addressprogrammed in the 40007 register NOTE The default manufacturer progr...

Отзывы: