  Serial iBootBar  v090212d 

 

 

Control Input Operation 

 
The eight control inputs can be used to operate the outlets.  Shorting any of the inputs to ground will change the state of the 
outlet with the same number as the input.  (Input 1 controls Outlet 1, Input 2 controls Outlet 2, etc.)   
 

Caution:

  Use only dry switch or relay closures, or open collector relay drivers to connect to the sBB inputs.  If you have any 

doubts about proper connections, consult Dataprobe Technical support. 

 
 
The default control is Input  Open = Outlet On, Input Grounded = Outlet Off.  
This can be changed using the 

set outlet <n> control.on <open/closed> 

command. 

 
Example: 

set outlet 3 control.on closed Causes 

Outlet three to be Input Closed (to Ground) = Outlet On, Input Open = Outlet Off 

get outlet 3 control.on

   

will check the current setting. 

 

 

 

Содержание sBB-N15

Страница 1: ...via RS 232 serial communications and via contact closure inputs The following models are covered in this document Model Power Feed Total Capacity Outlets sBB N15 NEMA 15 Amp 8 x NEMA 5 15 sBB 2N15 2 x...

Страница 2: ......

Страница 3: ...Instructions 4 Quick Start 5 General Overview 6 Installation 7 Rack Mounting Serial Port Contact Closure Inputs Power Source Serial Operation 9 Control Input Operation 14 Advanced Operation 15 Specif...

Страница 4: ...the grounding type plug Do not use a 3 to 2 prong adapter at the receptacle use of this type adapter may result in risk of electrical shock and or damage to this product 9 Do not allow anything to res...

Страница 5: ...t status iBootBar get outlets To turn on off outlet 1 iBootBar set outlet 1 off To reboot outlet 2 iBootBar set outlet 2 cycle Outlet Status Indicators Reset Pushbutton Recessed Mains Inlet Power Indi...

Страница 6: ...models Models with dual inputs sBB 2N or sBB 2C have two inlets mains Each main feeds four outlets Inlet A supports outlets 1 4 and Inlet B feeds 5 8 Dual power inlet models can be used to support hig...

Страница 7: ...outlets using contact closure contact open connections Each connection marked 1 through 8 controls the outlet of the same number The remaining 8 connections are ground and are interchangeable Using a...

Страница 8: ...Page 8 Serial iBootBar v090212d Expansion Future Expansion No function in the current Serial iBootBar...

Страница 9: ...al applications and can be used on 100V to 240VAC The sBB 2C10 provides two IEC 320 style universal inlets for connecting a detachable power cord Two standard IEC to CEE7 European cord sets are suppli...

Страница 10: ...must have rights to the selected outlet User set outlet 1 8 on off cycle Sets the selected outlet to the selected state The user must have rights to the selected outlet User set outlet 1 8 name name S...

Страница 11: ...Add user rights to outlets and groups Admin del user username Deletes the selected user from the root iBootBar s user table Admin ren user username newname Renames the selected user in the root iBootB...

Страница 12: ...ff during a reboot on off on or on during a cycle off on off User 10 get delay set delay 0 99 Get or set the delay time in seconds When multiple outlets are turned On by a single command this delay co...

Страница 13: ...in 120 set console baudrate 2400 4800 9600 19200 38400 57600 115200 The baud rate of the serial port 400 4800 9600 19200 38400 57600 115200 bps Admin 115200 set factory defaults Resets all parameters...

Страница 14: ...s or deletes a specific outlet on a specific device from the selected group Admin ren group groupname newname Renames the selected group 20 characters max Admin del group groupname Deletes the selecte...

Страница 15: ...y switch or relay closures or open collector relay drivers to connect to the sBB inputs If you have any doubts about proper connections consult Dataprobe Technical support The default control is Input...

Страница 16: ...es will be formatted as follows cr lf device name outlet outlet name control type source cr lf Where cr ASCII carriage return lf ASCII line feed character device name User programmed name of the sBB o...

Страница 17: ...load the latest version of the firmware and upgrade utility from the Dataprobe website Password Recovery Holding the reset button on the front panel of the iBootBar for 5 seconds or longer will initia...

Страница 18: ...I S M sBB 2N20 2 x N20 8 x N15 I S sBB 2N20 M 2 x N20 8 x N15 I S M sBB C10 C14 8 x C13 I S sBB C10 M C14 8 x C13 I S M sBB 2C10 2 x C14 8 x C13 I S sBB 2C10 M 2 x C14 8 x C13 I S M sBB C20 C20 8 x C1...

Страница 19: ...ies with Part 15 of the FCC rules Operation of this device is subject to the following conditions 1 This device may not cause harmful interference and 2 this device must accept any interference that m...

Страница 20: ...Technical Service at 201 934 5111 to receive a Return Materials Authorization RMA Number prior to sending any equipment back for repair Include all cables power supplies and proof of purchase with shi...

Отзывы: