background image

 

Series  K-x20, K-x15 & K-x10 

 

Page 3 

 

 

 
Remote Control and Feedback 

 

Two 9 pin female D-subminiature connector on the K-8xx series are used for connecting to the control 
and status feedback. The 

K-4xx

 

series

 has only one 9 pin d-subminiature connector and is supplied 

with  a cable for controlling it with one  of Dataprobe’s  xPal- 4xx series power switches. This cable 
enables  xPal-4xx unit to expand from 4 controlled outlets to 8. 
 
The wiring for the control port is identical on all units. The K-4xx series only uses Control and 
Feedback #s 1 – 4  See Wiring detail below. . If your controller does not use this cable, you will need 
to build one or order an additional cable from Dataprobe.  Refer to the control wiring details below for 
cable specification.    
 
The K-815 is factory wired to normally provide power to all the outlets. This is the default condition. 
When the control cable removed, all outlets will be power On.  The cable is designed to turn power 
OFF when a contact closure is made by the relay in the controlling device on the appropriate pins of 
the control cable. 
 
A positive feedback system is provided to insure that power control commands are achieved.   A  
feedback circuit for each outlet provides a Low (ground)  condition to indicate that power is On.  An 
Open condition indicates power Off.   
 

CONTROL WIRING:

   9 pin female  D-subminiature  

 
 Contact Closure between Control to Com = Power OFF 

 
 CONTROL #  PIN #            FEEDBACK#   PIN # 
 

J1/J2  

 

1/5 

 

2/6 

 

3/7 

 

4/8 

 

COM 

COM 

 

Example:

  To turn off outlet number one, connect the Control (Pin 1) to the Common (Pin 5).  The 

feedback on Pin 6 will change from Low (shorted to Pin 5) to Open. 
 
 

Standard Connections to Dataprobe Control Products 

 
Controlled by: 

Cables Required 

iP-410, -415, -420 

#1940052, Included w/ K-410, - 415, -420 if ordered together 

Cp-410, -415,-420 

#1940052, Included w/ K-410, - 415, -420 if ordered together 

MP-410 ,-415,-420 

#1940052, Included w/ K-410, - 415, -420 if ordered together 

iPAL, CodePAL, MultiPAL 

# 1940046 Qty 1 for K-4xx, Qty 2 for K-8xx series 

8PK-SCS 

# 1940046 Qty 1 for K-4xx, Qty 2 for K-8xx series  

ANN, MAC or EMAC 

# 1940048 

Отзывы: