 Multiple inputs on the local iPIO-8 can control the same relay on the remote unit.  In this case, the 
remote relay will switch based on the most recent input state change.  It is also possible to have the 
inputs of the local iPIO-8 control its own relays, by setting up a remote iPIO-8 with the local IP address. 
 
Click Save and the color Link Status will change from red to green to indicate successful 
communications between iPIO-8 devices.    
 
The Sync button allows information on all local inputs to be transmitted to the remote iPIO-8.  When the 
remote iPIO-8 is set up, use this button to coordinate the local inputs with the remote relays.   
 
iPIO-8 units continually communicate to coordinate inputs and outputs.  If one or more remotes are 
programmed, the RMT LED on the front of the iPIO-8 will be solid on.  If any remotes fail to 
communicate, the LED will flash, and the alarm relay (if programmed) will Open.  Click refresh, or 
refresh your browser window to view the latest remote status. 
 
If the Auto Update feature is enabled on the Device Setup section, the iPIO-8 will periodically transmit 
its status to the remote unit.  If the On Reconnect feature is enabled, the iPIO-8 will transmit its status 
whenever the connection to the remote is established or re-established. 
 

Содержание iPIO-8

Страница 1: ...Multiple iPIO 8 devices can communicate amongst themselves to transport I O information across the network Each iPIO 8 has eight controllable form C relays and eight digital inputs Each channel of the iPIO 8 is independently configurable allowing selection of what IP addresses to deliver to and on what channel Highly flexible telemetry systems can be developed with these simple devices REF ipio8_v...

Страница 2: ...PIO 8 relays using the screw terminals as illustrated Relays are Form C Connect to the Common C Normally Closed NC and Normally Open NO as marked When the iPIO 8 relay is in the Open Condition the Common is connected to the Normally Open In the Closed state the Common and Normally Closed are connected Relay Specifications Rating resistive 0 5 A 120 VAC or 1 A 24 VDC Maximum Carrying Current 2 A Ma...

Страница 3: ...Network Connect the network to the iPIO 8 with the Cat 5 cable provided or suitable replacement The Network connector on the iPIO 8 has two LED indicators The orange LINK LED indicates a successful connection to the network The Green ACT LED blinks to display network activity LED Indicators Pwr Power On indication Rmt Remote Communication Status indication LED OFF No Remote Units Programmed LED ON...

Страница 4: ...y Open LED ON Relay Closed During power up sequence LEDs will be off until boot complete then flash once then set to their current status Link Network Connected Act Network Activity During power up sequence Act LED will be solid on until boot process is complete After boot LED blinking indicates network activity ...

Страница 5: ...es the iPIO 8 device the user is connected to This location ID is settable Each input output and remote device is defined by a user selectable name Inputs and outputs can also be assigned names for Open and Closed statuses as well as background and text colors for each All configurations are accomplished via the Setup button at the left of the screen If the iPIO 8 is programmed to communicate with...

Страница 6: ...he user has access only to the status and control page The Administrator also has access to the setup pages Network Setup The iPIO 8 provides two methods for setting the IP Address 1 Static 2 DHCP Select Static Mode from the drop down list and fill in the IP Address Subnet Mask and Gateway as provided by your network administrator Click save to save the changes You will then be prompted to reboot ...

Страница 7: ...tion to secure status and control messages To use AES enter a AES Passphrase up to 16 characters and enable AES with the checkbox Any additional iPIO 8 that connects to this device will need to use the same Passphrase as set here See Remote Setup for entering the Passphrase of a remote iPIO 8 Use DxP Username and Password Older DxP supported devices do not use username and password pairs in the pr...

Страница 8: ...p on Change Set which events will generate SNMP Traps Input Email on any input change Relay Email on any relay change Communication Email on any change in communication status to the remotes Configuration Email on any configuration change To use the SNMP download the iPIO MIB at http dataprobe com support ipio8 Input Setup Each of the eight inputs is represented by a tab with its name Click on the...

Страница 9: ...ddress and Port if changed from default 9100 when setting up the remote AES Encryption can be used to secure communications with the remote Enter the Passphrase that matches the remote device and check the AES checkbox Remote Relays One relay on the local iPIO 8 can be used as an alarm for link failure When used the Alarm relay will be energized Common to Normally Closed connected when the link is...

Страница 10: ...ote iPIO 8 When the remote iPIO 8 is set up use this button to coordinate the local inputs with the remote relays iPIO 8 units continually communicate to coordinate inputs and outputs If one or more remotes are programmed the RMT LED on the front of the iPIO 8 will be solid on If any remotes fail to communicate the LED will flash and the alarm relay if programmed will Open Click refresh or refresh...

Страница 11: ...nk supervision add all the reporting sites as remotes in the central unit and set an alarm relay Application 3 Multi Site Event Distribution In this application one central sites broadcasts status information to multiple remote sites Set all remote sites as remotes in the central unit To get link supervision at the remote sites add the central unit as a remote and set an alarm relay in each locati...

Страница 12: ...e Discover from the menu to locate iPIO 8 units on the local network or Select Device Add from the menu to add the IP address of the iPIO 8 Once the device is displayed in the list highlight it 2 Select Manage Upgrade Firmware Enter User Name root and the Password for the Administrator default is admin Enter the filename of the firmware or click Browse and find the file of the firmware file to be ...

Страница 13: ...eset Hardware Reset Inputs 8 Digital Inputs Dry relay switch closures or 3VDC to 30 VDC Grounds common Control Relay Current Maximums 0 5A 120VAC or 1A 24VDC Switching Power 60VA Max 50uW Min Switching Voltage 120VAC or 60VDC Max 1VDC Min Switching Current 1A Max 1mA Min Resistance 100 milliohms initial value Operations 5 Million mechanical 100K at maximum load Network HTTP Web Server SSL Secure S...

Страница 14: ...ervice under this Warranty is obtained by contacting your Authorized Dataprobe Reseller THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT MISUSE ABUSE OR NEGLECT SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN EXCEPT TO THE EXTENT PROHIBITED BY LAW ALL IMPLIED WARRANTIES INCLUDING ALL WARRANTIES OF MERCHANT ABILITY OR FITNESS FOR...

Отзывы: