SG2 MUTING
47/96
Fig 59 - Muting T connection
Muting L
In L type operation the device enters Muting function if the inputs go high in a particular order: MUTING1 has to
activate first, then MUTING2 can activate; if MUTING2 activates before MUTING1, the device doesn’t enter the
Muting function.
“T12” is the activation delay between MUTING1 and MUTING2 that is selectable by the user by means of ACM.
The Muting function ends after a time that is a multiple of the activation delay between the two sensors (this time is
m * T12). The value of “m” (T12 multiplier) can be chosen by the user. In BCM this value is 2 by default.
The maximum activation delay between MUTING1 and MUTING2 can be set by the user from a minimum of 1 sec
to a maximum of 16 sec.
After this time if the user wants to enter in Muting has to deactivate the Muting input and start the sequence from
the beginning.
Fig 60 - Muting L timings
Muting L must be used exclusively for removing materials from the dangerous area.