LOW VOLTAGE ELECTRICAL CONNECTIONS
9
4
4.3 LASER BARCODE SCANNERS
4.3.1 Supply Capacity When Wiring Directly to AS-I Compatible
Scanners
For direct wiring, power distribution is performed simultaneously for all the scanners.
However all the scanner motors start up slowly so that there is no significant peak current
draw. See the specific scanner manual for consumption data.
The maximum number of same type scanners to be supplied for direct wiring by a single
PWR-480B is shown in the table below and depends on the wiring topology:
PWR-480B
Power Supply
Maximum Number of Scanners by Topology
Triple Branch
Double Branch
Single Branch
DS8110
22
18
9
DX8210
22
18
9
The following products are also AS-I compatible:
DS5100, DM3610, SC5000
. In case of
networks using a mix of products, you must calculate the total power consumption so as not
to exceed the limits for the specific topology used. See the specific product reference manual
in the Technical Features chapter for consumption data.
AS-I Single Branch
200 W max
AS-I Double Branch
200 W max per branch
AS-I Triple Branch
480 W max (200 W max per branch)
The power supply unit is connected directly to the scanners via AS-I cabling.
Figure 11 - Connecting PWR-480B Directly to Scanners
24 Vdc to scanners using AS-I cabling
AC in
DC OK (for REDs applications)