Datalogic BM100 Скачать руководство пользователя страница 2

NETWORK TYPE SELECTION 

 
The network type depends on the application layout and installed 
accessories. 
 
Through the CBX500 several types of accessory Fieldbus Interface 
Modules are available to connect to a Fieldbus as a Slave node. 
The Net Type switch setting must match the Host Interface 
accessory module being used. 
 
For all CBX series connection boxes the Net Type selector switch 
allows setting the ID-NET™ Slave type (Topology Role). This 
setting must match the Master ID-NET™ Topology Role. 
 
For CBX500 connection boxes the Net Type selector switch allows 
setting the Fieldbus type. 
 

Net Type Switch 
0 = None (no network present) 
1 = Ethernet IP 
2 = Profibus 
3 = DeviceNet 
4 = Reserved 
5 = Reserved 
6 = Reserved 
7 = Reserved 
8 = ID-NET™ Slave Synchronized 
9 = ID-NET™ Slave Multidata 

 
Fieldbus Slave nodes (including Masters with an ID-NET™ sub-
network) should be set to the specific Fieldbus type (

Ethernet

Profibus

, etc.). 

 
ID-NET™ Masters communicating with the Host through the main 
serial interface and all other non network applications should be 
set to 

None

 
If BM100s are used for ID-NET™ Slaves this switch should be set 
to the 

Slave Synchronized

 or 

Slave Multidata

 position depending 

on the ID-NET™ network Topology Role. 
 
 

NETWORK ADDRESS SELECTION 

 

 

Figure 3 – Address Selection Switches 

 
BM100 provides hardware network address selection for rapid 
installation. These switch settings override software configuration 
settings. Valid address selection depends on the network type: 
 

Ethernet 

The Ethernet address refers to the last three digits of the IP 
address (i.e. 172.16.1.xxx). The valid selection range is from 000 to 
255. Address selections outside of this range are not accepted by 
the Fieldbus network. 
 

Profibus 

The valid selection range for the Profibus address is from 000 to 
125. Address selections outside of this range are not accepted by 
the Fieldbus network. 
 

DeviceNet 

The valid selection range for the DeviceNet address is from 00 to 
63. Address selections outside of this range are not accepted by 
the Fieldbus network. The x100 switch is ignored. 
 

ID-NET™ 

The valid selection range for the ID-NET™ Slave addresses is 
from 01 to 31. Address selections outside of this range are not 
accepted by the ID-NET™ network. The x100 switch in this case 
refers to the ID-NET™ baudrate. 
 
 

BAUDRATE SELECTION 

 
All the Fieldbus networks use the autobaudrate feature. This 
means the reading devices automatically are set to use the 
Fieldbus baudrate. 

The Fieldbus baudrate cannot be set 

through the BM100 switches

 

 

Figure 4 – ID-NET™ Baudrate Switch 

 
When the BM100 is used for ID-NET™ network Slaves, the ID-
NET™ baudrate is selected through the baudrate switch and must 
match the Master ID-NET™ baudrate. The settings are: 
 

ID-NET™ Baudrate Switch 
0 = 19200 Baud 
1 = 38400 Baud 
2 = 57600 Baud 
3 = 125 kBaud 
4 = 250 kBaud 
5 = 500 kBaud 
6 = 1 MBaud 
7 = Reserved 
8 = Reserved 
9 = Reserved 

 

WRITE PROTECTION LOCK 

 

 

Figure 5 – Write Protection 

 
A write protection switch is provided to protect configuration data 
from being inadvertently overwritten. When this switch is in the lock 
position, the Backup function is not available (data cannot be 
written to the backup memory) and a diagnostic warning message 
can be sent. The Restore function is available. 
 
 

S/N LABEL 

 
A duplicate Serial Number label is included in the BM100 package. 
This label can be applied onto the outside of the CBX for quick 
reference. 
 
 

BM150 DISPLAY CONNECTOR 

 
BM100 provides the flat cable connector for connection of the 
BM150 Display and Keypad accessory for the CBX500. 
 
When the BM150 accessory is used the Backup and Restore 
functions are managed through the Display and Keypad and 
therefore are disabled at the BM100 Backup/Restore button. The 
BM150 has an extended menu which allows partial as well as 
complete backup and restore functions. 
 

Отзывы: