Datakom DPR-03 Скачать руководство пользователя страница 2

 

 

 

 

 
 
 

 

 

 

 
 

 

L1-L2-L3 :

 Phase voltages inputs 

1 :

 Relay output (NC)  

2 :

 Relay output (COM) 

3 :

 Relay output (NO) 

 
 
 
 
 
 
 
 

 

ON:

   Supply LED (green) 

OUT:

 Relay output LED (yellow) 

U<:

    Under Voltage Warning LED (red) 

U>:    

Over Voltage Warning LED (red) 

  

U< 

U> 

ON  OUT  MEANING 

 

 

ON 

ON 

Voltages OK 

ON 

 

ON 

ON 

Under voltage warning 

ON 

 

ON 

 

Under voltage trip 

 

ON 

ON 

ON 

Over voltage warning 

 

ON 

ON 

 

Over voltage trip 

FLASH 

ON 

 

Phase sequence trip 

 
 

 

Nominal Supply Voltage: 

400V-AC (L-L) 

Supply Voltage Range: 

260-520 V-AC (L-L) 

Supply type:

 Capacitive, 3 phase 

Frequency Range: 

47-63Hz  

Power Consumption:

 30VA / 2W  (max) 

Measurement method:

 True RMS, line to neutral 

Voltage Adjustment Accuracy:

 3 % 

Repetition Accuracy:

 0.5 % 

Over-Voltage Trip:

 400-520 V-AC (L-L)  

Under-Voltage Trip:

 240-360V-AC (L-L) 

Trip Delay Setup: 

0.5 

– 20 sec. adjustable

  

Reset Delay Setup: 

0.5 

– 20 sec. adjustable 

Relay Output:

 6A @ 277V-AC, 1800VA, 300W 

Terminal wire range

:  max 2.5mm² (12AWG)  

Screw-on Force:

 0.4 Nm (3.6 lb.in) 

Operating temp.:

 -30

C (-22

F) to 70 

C (158

F). 

Storage temp.:

    -40

C (-40

F) to 80 

C (176

F). 

Maximum humidity:

 95% non-condensing. 

Dimensions:

 36,0x90,6x58,4mm (WxHxD) 

Weight:

 100 gr(approx.) 

Installation:

 DIN Rail mounted.  

Case Material:

 High Temp. ABS/PC (UL94-V0) 

IP Protection:

 IP30 

Conformity (EU directives) 

 

-2006/95/EC (low voltage)

 

 

-2004/108/EC (EMC) 

Norms of reference: 

 

EN 61010  (safety requirements) 

             EN 60255-6 
             EN 61326  (EMC requirements) 

 

 

      

            

 

LED INDICATORS 

 

DIMENSIONS 

 

TECHNICAL SPECIFICATIONS 

 

INPUTS AND OUTPUTS 

 

INSTALLATION DIAGRAM 

 

Отзывы: