L1-L2-L3 :
Phase voltages inputs
1 :
Relay output (NC)
2 :
Relay output (COM)
3 :
Relay output (NO)
ON:
Supply LED (green)
OUT:
Relay output LED (yellow)
U<:
Under Voltage Warning LED (red)
U>:
Over Voltage Warning LED (red)
U<
U>
ON OUT MEANING
ON
ON
Voltages OK
ON
ON
ON
Under voltage warning
ON
ON
Under voltage trip
ON
ON
ON
Over voltage warning
ON
ON
Over voltage trip
FLASH
ON
Phase sequence trip
Nominal Supply Voltage:
400V-AC (L-L)
Supply Voltage Range:
260-520 V-AC (L-L)
Supply type:
Capacitive, 3 phase
Frequency Range:
47-63Hz
Power Consumption:
30VA / 2W (max)
Measurement method:
True RMS, line to neutral
Voltage Adjustment Accuracy:
3 %
Repetition Accuracy:
0.5 %
Over-Voltage Trip:
400-520 V-AC (L-L)
Under-Voltage Trip:
240-360V-AC (L-L)
Trip Delay Setup:
0.5
– 20 sec. adjustable
Reset Delay Setup:
0.5
– 20 sec. adjustable
Relay Output:
6A @ 277V-AC, 1800VA, 300W
Terminal wire range
: max 2.5mm² (12AWG)
Screw-on Force:
0.4 Nm (3.6 lb.in)
Operating temp.:
-30
C (-22
F) to 70
C (158
F).
Storage temp.:
-40
C (-40
F) to 80
C (176
F).
Maximum humidity:
95% non-condensing.
Dimensions:
36,0x90,6x58,4mm (WxHxD)
Weight:
100 gr(approx.)
Installation:
DIN Rail mounted.
Case Material:
High Temp. ABS/PC (UL94-V0)
IP Protection:
IP30
Conformity (EU directives)
-2006/95/EC (low voltage)
-2004/108/EC (EMC)
Norms of reference:
EN 61010 (safety requirements)
EN 60255-6
EN 61326 (EMC requirements)
LED INDICATORS
DIMENSIONS
TECHNICAL SPECIFICATIONS
INPUTS AND OUTPUTS
INSTALLATION DIAGRAM