Datakom DPR-03 Скачать руководство пользователя страница 1

 

DPR-03 relay is a three-phase (line to line) 
voltage protection relay designed to be used for 
over-voltage, under-voltage and phase rotation  
protection in distribution substations, generators, 
motors, transformers and capacitors in 
compensation systems. 

It offers adjustable over / under voltage limits 
together with adjustable trip and reset delays. The 
unit has also phase sequence protection. 

Both over voltage limit(Max) and under voltage 
limit(Min) can be adjusted or disabled via 
trimmers on the front panel of the device. Delay 
timers are adjusted through related trimmers.

 

 

VOLTAGE PROTECTION 

If any of phase voltages goes over the set MAX 
limit, the 

U>

” led turns on and the adjusted Delay 

timer starts to count. If the fault condition 
disappears before the Delay timer expires, then 
the

U>

” led turns off. If the fault condition persists 

until the expiration of the Delay timer, the relay 
output is deactivated 

and the “

OUT

” led turns off.  

If any of measured voltages goes below the set 
MIN limit, the 

U<

” led turns on and the adjusted 

Delay timer starts to count. If the fault condition 
disappears before the Delay timer expires, then 
the

U<

” led turns off. If the fault condition persists 

until the expiration of the Delay timer, the relay 
output is deactivated 

and the “

OUT

” led turns off.  

When the MAX or MIN Voltage trimmer is 
adjusted to the 

OFF

” position, the related voltage 

protection will be disabled. 

When all voltages are again within adjusted MIN-
MAX limits,   

U<

” and “

U>

” leds turn off and the 

adjusted Reset Delay timer starts to count. When 
the timer is expired, the relay output is activated 
and the 

OUT

” led turns on. 

PHASE FAILURE PROTECTION 

If the voltage of any phase falls below 65% of the 
nominal value, then 

U<

” led turns on and 

immediately the relay output is deactivated and 
the “

OUT

” led turns off. 

OVERVOLTAGE PROTECTION 

If the any phase voltage goes 50% above the 
nominal value, then 

U>

” led turns on and 

immediately the relay output is deactivated and 
the “

OUT

” led turns off. 

PHASE SEQUENCE PROTECTION 

If the phase sequence is reversed, both 

U<

” and 

U>

” leds flash, the relay output is deactivated 

and the “

OUT

” led turns off.   

 

* Electrical equipment should be installed only by 
qualified specialist. No responsibility is assured by 
the manufacturer or any of its subsidiaries for any 
consequences resulting from the non-compliance 
to these instructions. 
* Check the unit for cracks and damages due to 
transportation. Do not install damaged equipment. 
* Do not open the unit. There is no serviceable 
parts inside. 
* Fuses of fast type (FF) with a maximum rating of 
6A must be connected to phase voltage inputs, in 
close proximity of the unit. 
* Disconnect all power before working on 
equipment. 
* When the unit is connected to the network do 
not touch terminals. 
* Any electrical parameter applied to the device 
must be in the range specified in the user manual. 
* Do not try to clean the device with solvent or the 
like. Only clean with a dump cloth. 
* Do not allow water to come inside the unit. 
* Verify correct terminal connections before 
applying power. 
* Only for DIN rail mounting. 

 

Before installation: 

 Read this manual carefully, determine the 

correct connection diagram. 

 Make sure to use adequate fuses.

 

 Do not subject the unit to water spill.

 

Below conditions may damage the device: 

 Incorrect connections. 

 Incorrect power supply voltage. 

 Overload or short circuit at relay outputs 

 Power supply frequency out of specified limits 

 

 

Do not install the unit close to high 
electromagnetic noise emitting devices like 
contactors, high current busbars, switchmode 
power supplies and the like. Although the unit 
is protected against electromagnetic 
disturbances, excessive disturbance can affect 
the operation and measurement precision. 

  Use adequate cable section, at least 0.75mm

(AWG18).  

 

 

OPERATION

 

 

Do not overload relay 
outputs. Use extra 
contactors if required. 

 

ELECTRICAL INSTALLATION 

 

PRE-INSTALLATION

 

 

SAFETY NOTICE  
Failure to follow below 
instructions will result in 
death or serious injury

 

 

DPR-03 VOLTAGE 

PROTECTION RELAY 

(LINE TO LINE) 

 