DKM-411 Modbus Application Manual V3.0
(15.01.2017)
- 11 -
ADDRESS
(decimal)
R / W
DATA
SIZE
COEFF.
DESCRIPTION
8192
R / W
16bit
-
Year (0-4095)
8193
R / W
16bit
-
Month (1-12)
8194
R / W
16bit
-
Date (1-31)
8195
R
16bit
-
Day of Week (0-6)
8196
R / W
16bit
-
Hours (0-23)
8197
R / W
16bit
-
Minutes (0-59)
8198
R / W
16bit
-
Seconds (0-59)
8199
R / W
16bit
-
Year (0-4095) (UTC)
8200
R / W
16bit
-
Month (1-12) (UTC)
8201
R / W
16bit
-
Date (1-31) (UTC)
8202
R
16bit
-
Day of Week (0-6) (UTC)
8203
R / W
16bit
-
Hours (0-23) (UTC)
8214
R / W
16bit
-
Minutes (0-59) (UTC)
8215
R / W
16bit
-
Seconds (0-59) (UTC)
ADDRESS
(decimal)
R / W
DATA
SIZE
COEFF.
DESCRIPTION
12288
R / W
32bit
x10
kWh_1 import
12290
R / W
32bit
x10
kWh_1 export
12292
R / W
32bit
x10
kVArh_1 inductive
12294
R / W
32bit
x10
kVArh_1 capacitive
12296
R / W
32bit
x10
Group_1 Hour Counter
12298
R / W
32bit
x10
kWh_2 import
12300
R / W
32bit
x10
kWh_2 export
12302
R / W
32bit
x10
kVArh_2 inductive
12304
R / W
32bit
x10
kVArh_2 capacitive
12306
R / W
32bit
x10
Group_2 Hour Counter
12332
R / W
32bit
x1
Digital Input 1 Counter
12334
R / W
32bit
x1
Digital Input 2 Counter
REGISTER DEFINITIONS