K30D01-EN - 23 - Version 1.5
4.16. CONFIGURING THE RELAY OUTPUT
SET
MENU
MENU
PGM
rELY
FnC1
1
The relay output is a combination of 4
different input functions. The combination
logic is explained in the next picture.
Each of 4 available functions is selected
from the below list. Unused functions
should be left as 0.
Value Relay Function
0
-
1
Follows the digital input
2
kWh tick
3
kVArh tick
4
High voltage alarm
5
Low voltage alarm
6
High frequency alarm
7
Low frequency alarm
8
Overcurrent alarm
9
Excess active power alarm
10
Low active power alarm
11
Excess reactive power alarm
12
Low reactive power alarm
13
High cosø alarm
14
Low cosø alarm
15
Phase sequence alarm
16
Relay active if any alarm exists
SET
MENU
MENU
PGM
rELY
LoJt
0
The relay output is the combination of 4
functions defined above. Thus various
combined functions may be attributed to
the relay output.
This parameter defines how functions are
combined in order to generate the relay
output.
0:
Functions logically OR’ed. The relay
output is active if any of the 4 functions is
active.
1:
Functions loagically AND’ed. The relay
output is active if all 4 functions are active.