DKG-225 User Manual Firmware V-01
- 25 -
STOPPING THE GENSET:
Press STOP
button
STARTING THE GENSET:
Press RUN
button
AUTOMATIC OPERATION:
Press AUTO
button.
The STOP mode is entered by pressing the
button.
In this mode, the genset will be in a rest state.
When STOP mode is selected, if the genset is running under load, then it will be immediately unloaded.
The engine will continue to run during
Cooldown Timer
and will stop afterwards.
If the STOP button is pressed again, then the engine will immediately stop.
If the engine fails to stop after the expiration of
Stop Timer
then a
Fail to Stop
warning will occur.
In this mode, the mains contactor will be energized only if mains phase voltages and frequency are within
the programmed limits. If enabled, the mains phase order is also checked.
The RUN mode is entered by pressing the
button.
When the RUN mode is selected, the engine will be started regardless of the mains availability.
In order to stop the genset please press
button or select another operating mode.
If Emergency Backup mode is enabled and if the mains are
off, then the mains contactor will be deactivated and the
generator contactor will be activated.
When the mains are on again, a reverse changeover to the
mains will be performed, but the engine will keep running
unless another mode is selected.
Mode can be changed anytime without negative effect.
Changing the operation mode while the genset is running will
result into a behavior suitable for the new operating mode.
8.3. MANUAL RUN MODE
8.2. STOP MODE
8.1. QUICK START GUIDE
8. OPERATION OF THE UNIT