DKG-190 User Manual V-1.1
(24.03.2015)
-3-
Although the unit is protected against electromagnetic disturbance, excessive disturbance
can affect the operation, measurement precision and data communication quality.
ALWAYS remove plug connectors when inserting wires with a screwdriver.
Fuses must be connected to supply inputs, in close proximity of the unit.
Fuses must be of fast type (FF) with a maximum rating of 6A.
Use cables of appropriate temperature range.
Use adequate cable section, at least 0.75mm
2
(AWG18).
DC Supply Range:
19.0 - 70.0 V-DC.
Power Consumption:
< 4W
Alternator Voltage:
0 - 300 V-AC (L-N)
Alternator Frequency:
45-65 Hz.
Mains Voltage:
0 - 300 V-AC (L-N)
Mains Frequency:
45-65 Hz
AC Voltage Accuracy:
±2V
DC Voltage Accuracy:
±0.2V
AC Output:
Voltage Range:
70-260VAC
Output Power:
0.5VA max
Min. Load Impedance:
100 k-ohms
Frequency Range:
45-65Hz
Regulation:
PID
Operating Temp Range:
-
20°C to 70°C
Storage Temp Range:
-
40°C to 80°C
Max. Relative Humidity:
95% non-condensing
IP Protection:
IP30
Dimensions:
133 x 107 x 46mm (WxHxD)
Weight:
350 g (approx.)
Case Material:
High temperature, flame retardant
ABS/PC (UL94-V0)
Installation:
DIN Rail mounted
EU Directives:
2006/95/EC (LVD)
2004/108/EC (EMC)
Reference Standards:
EN 61010 (safety)
EN 61326 (EMC)
ELECTRICAL INSTALLATION
Do not install the unit close to high electromagnetic
noise emitting devices like contactors, high current
busbars, switchmode power supplies and the like.
Be sure that the AC output is not overloaded.
TECHNICAL SPECIFICATIONS