DKG-190 User Manual                                                                           V-1.1 

(24.03.2015) 

 

-3- 

 

 

 

 

 

 

Although the unit is protected against electromagnetic disturbance, excessive disturbance 
can affect the operation, measurement precision and data communication quality. 

 

 

ALWAYS remove plug connectors when inserting wires with a screwdriver. 

 

Fuses must be connected to supply inputs, in close proximity of the unit. 

 

Fuses must be of fast type (FF) with a maximum rating of 6A. 

 

Use cables of appropriate temperature range. 

 

Use adequate cable section, at least 0.75mm

(AWG18).  

 

 
 
 

 

DC Supply Range: 

19.0 - 70.0 V-DC. 

Power Consumption: 

< 4W 

Alternator Voltage: 

0 - 300 V-AC (L-N) 

Alternator Frequency: 

45-65 Hz. 

Mains Voltage: 

0 - 300 V-AC (L-N) 

Mains Frequency: 

45-65 Hz

 

AC Voltage Accuracy: 

±2V 

DC Voltage Accuracy: 

±0.2V 

AC Output: 
      Voltage Range:             

70-260VAC 

      

Output Power:

               0.5VA max 

      

Min. Load Impedance:

 100 k-ohms 

      Frequency Range:

        45-65Hz 

      

Regulation:

                    PID 

 

Operating Temp Range: 

-

20°C to 70°C  

Storage Temp Range: 

-

40°C to 80°C 

Max. Relative Humidity: 

95% non-condensing 

IP Protection: 

IP30  

Dimensions: 

133 x 107 x 46mm (WxHxD) 

Weight: 

350 g (approx.) 

Case Material: 

High temperature, flame retardant 

ABS/PC (UL94-V0) 

Installation:

 DIN Rail mounted 

 

EU Directives:

  

2006/95/EC (LVD)

 

2004/108/EC (EMC) 

Reference Standards:

 

EN 61010 (safety) 
EN 61326 (EMC) 

 

 

ELECTRICAL INSTALLATION

 

 

Do not install the unit close to high electromagnetic 
noise emitting devices like contactors, high current 
busbars, switchmode power supplies and the like. 

 

 

Be sure that the AC output is not overloaded. 

 

TECHNICAL SPECIFICATIONS

 

Содержание DKG-190

Страница 1: ...s the genset to run The genset runtime is adjusted on the DKG 190 When this timer is expired the unit sends again the AC voltage to the genset controller causing the genset to stop The genset stays in rest until batteries are discharged again When the mains is restored the genset stops regardless of the battery charge status The unit measures and displays precisely battery genset and mains voltage...

Страница 2: ...st be in the range specified in the user manual Do not try to clean the device with solvent or the like Only clean with a dry cloth Verify correct terminal connections before applying power Before installation Read the user manual carefully determine the correct connection diagram Install the unit to the DIN rail Make electrical connections with plugs removed from sockets then place plugs to their...

Страница 3: ...ge 0 300 V AC L N Mains Frequency 45 65 Hz AC Voltage Accuracy 2V DC Voltage Accuracy 0 2V AC Output Voltage Range 70 260VAC Output Power 0 5VA max Min Load Impedance 100 k ohms Frequency Range 45 65Hz Regulation PID Operating Temp Range 20 C to 70 C Storage Temp Range 40 C to 80 C Max Relative Humidity 95 non condensing IP Protection IP30 Dimensions 133 x 107 x 46mm WxHxD Weight 350 g approx Case...

Страница 4: ...DKG 190 User Manual V 1 1 24 03 2015 4 INSTALLATION DIAGRAM ...

Страница 5: ...tage is low VDC LED Turns on when the battery voltage is displayed HOURS LED Turns on when the screen displays the running timer BUTTON FUNCTION Switches the screen to the next parameter HELD PRESSED DURING 3 SECONDS The genset goes to the TEST mode The engine will run during the adjusted test timer and then stops If any button is pressed during the test the genset stops immediately Programming mo...

Страница 6: ...ays the name of the parameter If the Menu button is held pressed for 3 seconds the value of the parameter to change is brought to screen Adjust the parameter by using the arrow buttons In order to increase decrease faster please hold the button pressed Pressing the Menu button will cause the parameter value to be written to memory and the display to switch to the next parameter BUTTON OPERATION SC...

Страница 7: ...een the mains is restored and the genset stops The format is Minute Second 0 30min MAINS VOLTAGE LOW LIMIT Below this limit the mains phase voltage is supposed to fail 70V 270V MAINS VOLTAGE HIGH LIMIT Above this limit the mains voltage is supposed to fail 100V 300V LAMP TEST If the arrow up button is held pressed for 3 seconds the Lamp Test mode will start In this mode all lights will turn on Aft...

Страница 8: ...IMER This is the period of test run The format is Minute Second 1 30min AC OUTPUT VOLTAGE The AC voltage produced by the controller is defined by this parameter The usual value is 230V 40V 270V AC OUTPUT FREQUENCY The frequency of the AC voltage produced by the controller is defined by this parameter The usual value is 50 or 60 Hz 50Hz 60Hz DATAKOM Elektronik Ltd Tel 90 216 466 84 60 Fax 90 216 36...

Отзывы: