DKG-190 User Manual                                                                           V-1.1 

(24.03.2015) 

 

-1- 

 

 

 

  

DKG-190 

BATTERY CHARGE 
CONTROLLER 

 

 

The DKG-190 is a high-tech product designed to 
decrease operating engine hours of gensets used 
in telecommunication systems. 

The unit brings considerable economies to genset 
run-hours, fuel consumption and service cost. 

In simple telecom systems, gensets run during 
mains failure periods. Thus the genset run hour is 
equal to the sum of mains failure hours. 

The DKG-190 feeds the existing genset control 
unit with the AC voltage that it generates 
internally and prevents the engine from running 
when not necessary. It can be adapted to any 
brand and model of genset control unit. 

When the mains is off, the DKG-190 continues to 
feed the genset controller with AC voltage and 
monitors the battery voltage. When the battery 
voltage falls below the preprogrammed level, then 
it cuts the AC voltage and causes the genset to 
run. 

The genset runtime is adjusted on the DKG-190. 
When this timer is expired, the unit sends again 
the AC voltage to the genset controller causing 
the genset to stop. The genset stays in rest until 
batteries are discharged again. 

When the mains is restored, the genset stops 
regardless of the battery charge status. 

The unit measures and displays precisely battery, 
genset and mains voltages. 

The AC voltage generated by the unit is a pure 
sinus with adjustable voltage and frequency. 
These features are obtained thanks to the high 
voltage PWM control and PID loop. 

The unit can be virtually adapted to any genset 
controller thanks to its adjustable parameters. 

 

 

 

 

Supports both 24V and 48V DC systems 

 

Supply voltage range: 19-70VDC 

 

Accurate DC voltage measurement 

 

True RMS mains/genset voltage measurements 

 

Adjustable and PID controlled AC output 

 

Adjustable AC output frequency 

 

Pure sinus AC output voltage 

 

Genset test capability 

 

Adjustable parameters 

 

DIN rail mounted 

 

Small dimensions 

 

Wide operating temperature range 

 

2 part connection system 

 

     

 

    

 

 

DESCRIPTION

 

FEATURES

 

Содержание DKG-190

Страница 1: ...s the genset to run The genset runtime is adjusted on the DKG 190 When this timer is expired the unit sends again the AC voltage to the genset controller causing the genset to stop The genset stays in rest until batteries are discharged again When the mains is restored the genset stops regardless of the battery charge status The unit measures and displays precisely battery genset and mains voltage...

Страница 2: ...st be in the range specified in the user manual Do not try to clean the device with solvent or the like Only clean with a dry cloth Verify correct terminal connections before applying power Before installation Read the user manual carefully determine the correct connection diagram Install the unit to the DIN rail Make electrical connections with plugs removed from sockets then place plugs to their...

Страница 3: ...ge 0 300 V AC L N Mains Frequency 45 65 Hz AC Voltage Accuracy 2V DC Voltage Accuracy 0 2V AC Output Voltage Range 70 260VAC Output Power 0 5VA max Min Load Impedance 100 k ohms Frequency Range 45 65Hz Regulation PID Operating Temp Range 20 C to 70 C Storage Temp Range 40 C to 80 C Max Relative Humidity 95 non condensing IP Protection IP30 Dimensions 133 x 107 x 46mm WxHxD Weight 350 g approx Case...

Страница 4: ...DKG 190 User Manual V 1 1 24 03 2015 4 INSTALLATION DIAGRAM ...

Страница 5: ...tage is low VDC LED Turns on when the battery voltage is displayed HOURS LED Turns on when the screen displays the running timer BUTTON FUNCTION Switches the screen to the next parameter HELD PRESSED DURING 3 SECONDS The genset goes to the TEST mode The engine will run during the adjusted test timer and then stops If any button is pressed during the test the genset stops immediately Programming mo...

Страница 6: ...ays the name of the parameter If the Menu button is held pressed for 3 seconds the value of the parameter to change is brought to screen Adjust the parameter by using the arrow buttons In order to increase decrease faster please hold the button pressed Pressing the Menu button will cause the parameter value to be written to memory and the display to switch to the next parameter BUTTON OPERATION SC...

Страница 7: ...een the mains is restored and the genset stops The format is Minute Second 0 30min MAINS VOLTAGE LOW LIMIT Below this limit the mains phase voltage is supposed to fail 70V 270V MAINS VOLTAGE HIGH LIMIT Above this limit the mains voltage is supposed to fail 100V 300V LAMP TEST If the arrow up button is held pressed for 3 seconds the Lamp Test mode will start In this mode all lights will turn on Aft...

Страница 8: ...IMER This is the period of test run The format is Minute Second 1 30min AC OUTPUT VOLTAGE The AC voltage produced by the controller is defined by this parameter The usual value is 230V 40V 270V AC OUTPUT FREQUENCY The frequency of the AC voltage produced by the controller is defined by this parameter The usual value is 50 or 60 Hz 50Hz 60Hz DATAKOM Elektronik Ltd Tel 90 216 466 84 60 Fax 90 216 36...

Отзывы: