Datakom DKG-155 Скачать руководство пользователя страница 2

 

 

 

 

 

 

 

 
DC SUPPLY:

 12 or 24 volts DC, (+) and (-) terminals. 

L1:

 Generator phase voltage. 

NEUTRAL:

 Generator neutral terminal. 

HIGH TEMP SWITCH:

 Negative closing switch input. 

LOW OIL PRESSURE:

 Negative closing switch input. 

SPARE:

  Spare  fault  input.  A  negative  supply 

connection  to  this  input  will  cause  the  engine 
immediately stopped and an alarm given (independent 
of the protection hold-off timer). 

CHARGE:

 

Connect  the  charge  alternator’s  D+  end  to 

this  terminal.  This  terminal  will  supply  the  excitation 
current  and  measure  the  voltage  of  the  charge 
alternator. 
 

 

 
FUEL SOLENOID 

:

 16amps@28V-DC. 

START   

:

 16amps@28V-DC. 

ALARM   

:

 16amps@28V-DC. 

 

 

 
STANDARD FEATURES: 

50Hz nominal, 

OPTIONAL FEATURES: 
(SUBJECT TO SPECIAL ORDER) 

60Hz nominal. 
 

 

 
Alternator Voltage: 

15 to 300 V-AC 

Alternator Frequency:

 50 or 60 Hz nominal. 

Overspeed:

 nominal fre 14% 

 

      (+24% overshoot) 

Underspeed:

 30Hz 

DC Supply Range:

 9 to 33 V-DC. 

Current consumption:

 150mA max. (Relay outputs 

open). 

Charge fail threshold:

 6 V-DC. 

Charge excitation current:

 via 220 ohms resistor 

connected to the 

FUEL

 output. 

Operating temp.:

 -20

C (-4

F) to 70 

C (158

F). 

Storage temp.:

    -30

C (-22

F) to 80 

C (176

F). 

Maximum humidity:

 95% non-condensing. 

Dimensions:

 72x72x52mm (WxHxD) 

Panel cutout dimensions:

 68x68 mm 

Weight:

 220g (approx.) 

Installation:

 Front panel mounted. Retaining steel 

spring provided. 
 
 
 
 
 
 
 

        DATAKOM Electronics Ltd.                                           

Tel: +90-216-466 84 60   Fax: +90-216-364 65 65   e-mail: [email protected]   http: www.datakom.com.tr 

TECHNICAL SPECIFICATIONS

 

OPTIONS

 

OUTPUTS

 

INPUTS

 

TYPICAL CONNECTION DIAGRAM 

 