DC SUPPLY:
12 or 24 volts DC, (+) and (-) terminals.
L1:
Generator phase voltage.
NEUTRAL:
Generator neutral terminal.
HIGH TEMP SWITCH:
Negative closing switch input.
LOW OIL PRESSURE:
Negative closing switch input.
SPARE:
Spare fault input. A negative supply
connection to this input will cause the engine
immediately stopped and an alarm given (independent
of the protection hold-off timer).
CHARGE:
Connect the charge alternator’s D+ end to
this terminal. This terminal will supply the excitation
current and measure the voltage of the charge
alternator.
FUEL SOLENOID
:
16amps@28V-DC.
START
:
16amps@28V-DC.
ALARM
:
16amps@28V-DC.
STANDARD FEATURES:
50Hz nominal,
OPTIONAL FEATURES:
(SUBJECT TO SPECIAL ORDER)
60Hz nominal.
Alternator Voltage:
15 to 300 V-AC
Alternator Frequency:
50 or 60 Hz nominal.
Overspeed:
nominal fre 14%
(+24% overshoot)
Underspeed:
30Hz
DC Supply Range:
9 to 33 V-DC.
Current consumption:
150mA max. (Relay outputs
open).
Charge fail threshold:
6 V-DC.
Charge excitation current:
via 220 ohms resistor
connected to the
FUEL
output.
Operating temp.:
-20
C (-4
F) to 70
C (158
F).
Storage temp.:
-30
C (-22
F) to 80
C (176
F).
Maximum humidity:
95% non-condensing.
Dimensions:
72x72x52mm (WxHxD)
Panel cutout dimensions:
68x68 mm
Weight:
220g (approx.)
Installation:
Front panel mounted. Retaining steel
spring provided.
DATAKOM Electronics Ltd.
Tel: +90-216-466 84 60 Fax: +90-216-364 65 65 e-mail: [email protected] http: www.datakom.com.tr
TECHNICAL SPECIFICATIONS
OPTIONS
OUTPUTS
INPUTS
TYPICAL CONNECTION DIAGRAM