background image

 

 

 

 

 

DKG-154  

REMOTE START UNIT 

INSTALLATION AND OPERATING INSTRUCTIONS

 

 

 

 

 

The  DATAKOM  model  DKG-154  is  a  low  cost, 
microprocessor  controlled  unit  designed  to  start 
and stop the genset automatically on request of an 
external Remote Start signal.  

When the engine is running, the unit monitors fault 
conditions and shuts-down the engine automatically 
in  the  occurrence  of  an  alarm.  The  alarms  are 
identified  by  a  group  of  LEDs  displaying  only  the 
first occurring one. 

The  unit  has  jumper  selectable  options  for  the 
auxiliary  relay  output  function.  The  selection  is 
made by the position of a single jumper situated at 
the left side panel of the unit. 

If the jumper is placed between: 
A & B :

 50 Hz nominal, AUX is Preheat output 

B & C :

 60 Hz nominal, AUX is Preheat output 

C & D :

 60 Hz nominal, AUX is Stop output 

D & A :

 50 Hz nominal, AUX is Stop output 

In the 

OFF

 position, the DC supply is removed from 

the module, thus remote start operation is disabled 
and zero power consumption is achieved. 

 

The unit powers up when the 

AUTO

 position on the 

front panel is selected. It will start the engine when 
its Remote Start input is pulled to battery negative 
and will act like below: 

If 

‘Preheat’

 option is selected, it energizes the 

AUXILIARY

 output for 

Preheat Delay

, then 

releases it. 

Then it energizes the 

FUEL

 output for 

Wait Before 

Start

 delay, then energizes the 

START

 output for 

Start Duration

. If the engine fires, the start output 

is immediately released. The protections will be 
enabled only after the 

Protection Hold-off Timer

 

has expired. 

If the engine does not fire, start and fuel outputs are 
deenergized, if 

‘Preheat’

 option is selected, the 

AUXILIARY

 output will be energized and the unit 

will wait for 

Wait Between Starts

 period before a 

new crank cycle is initiated. The engine is cranked 
up to 3 times. 

If the Remote Start signal disappears while the 
engine is running, the engine will continue to run for 

Cooldown Duration

. Then the fuel output is 

deenergized, if the 

‘Activate to Stop’

 option is 

selected, the 

AUXILIARY

 output will be energized 

for 

Stop Timer

, and the unit will be ready for a new 

Remote Start. 

The 

PREHEAT/STOP  (

led  will  continuously 

indicate the 

AUXILIARY

 output status. 

The occurrence of below fault conditions will cause 
the engine to be stopped immediately: 

       -Overspeed, 
       -Underspeed, 
       -High engine temperature, 
       -Low oil pressure, 

If  a  fault  condition  occurs,  the 

FUEL

  solenoid  will 

be  deenergized.  I

f the ‘

Energize to Stop

’ option is 

selected,  the 

AUXILIARY

  output  will  be  energized 

during 

Stop Timer

 and the led associated with this 

fault condition will turn on.  

Only  the  first  occurring  fault  will  be  indicated.  To 
reset the fault condition, turn the switch to the 

OFF

 

position for a few seconds. 

The 

Charge  Fail 

condition  is  treated  as  a  warning 

only and do not cause the engine to stop. The input 
monitors the 

D+

 terminal of the charge alternator. 

OPERATION

 

DESCRIPTION

 

Отзывы: