DKG-119 User Manual V-27
(20.04.2012)
- 30 -
Program Group: Electrical Parameters
Parameter Definition,
(Password Level)
Unit Factory
Set
Description
(2)
Current Transformer
Ratio
A
500
This is the rated value of the current transformer.
The secondary of the transformer will be 5 Amps.
(2)
Overcurrent Limit
A
0
If the current goes above this limit, during
Overload
Timeout
then a
Overcurrent Load Dump
alarm will be
generated. If this parameter is 0 then Overcurrent check
is disabled.
(2)
Power x 3
-
0
If this parameter is set to 1, then the power read from
the genset phase will be displayed as multiplied by 3.
(2)
Excess Power Limit
KW
0
If the active power goes above this limit, during
Overload Timeout then an
Excess Power Load Dump
alarm will be generated. If this parameter is 0 then
Excess Power check is disabled.
(2)
Overload Timeout
sec
5
This is the period between the current or active power go
over the limits and
OVERCURRENT
or
EXCESS
POWER
Load Dump alarms occur.
This is also the period between the frequency goes out
of the limits and
OVERSPEED
or
UNDERSPEED
alarms
occur.
This is also the period between the genset voltage goes
out of the limits and
HIGH VOLTAGE
or
LOW
VOLTAGE
alarms occur.
(2)
Genset Voltage Low
Limit
V
170
If one of the generator phase voltages goes under this
limit when feeding the load, this will generate a
GENSET
LOW VOLTAGE
alarm
and the engine will stop.
(2)
Genset Voltage High
Limit
V
270
If one of the generator phase voltages goes over this
limit when feeding the load, this will generate a
GENSET
HIGH VOLTAGE
alarm and the engine will stop.
(2)
Low Battery Voltage
Warning
V
9.0
If the battery voltage falls below this limit, this will
generate a
LOW BATTERY
warning.
(2)
High Battery Voltage
Warning
V
31.0
If the battery voltage goes over this limit, this will
generate a
HIGH BATTERY
warning.
(2)
High Battery Voltage
Shutdown
V
33.0
If the battery voltage goes over this limit, this will
generate a
HIGH BATTERY
shutdown
alarm and the
engine will stop.
(1)
Mains Waiting Timer
min
0.5
This is the time between the mains voltages entered
within the limits and the generator contactor is
deactivated.
(2)
Genset Contactor Timer
sec
1
This is the period after the mains contactor has been
deactivated and before the generator contactor has been
activated.
(2)
Mains Contactor Timer
sec
1
This is the period after the generator contactor has been
deactivated and before the mains contactor has been
activated.
(2)
Reverse power warning
limit
KW
0
If the genset power is negative and goes above this
limit then a
REVERSE POWER
warning will be
generated.
(2)
Reverse power
loaddumpg limit
KW
0
If the genset power is negative and goes above this
limit then a
REVERSE POWER
loaddump will be
generated.
(2)
Load Shedding Low
Limit
KW
0
If the genset power goes below this limit then the load
shedding relay will be deactivated.
(2)
Load Shedding High
Limit
KW
0
If the genset power goes above this limit then the load
shedding relay will be activated.