background image

FITTING AND  OPERATING

STABILITY ADJUSTMENT

The AVR  includes a  stability or damping circuit to  provide 

good  steady  state  and  transient  performance  of  the 
generator.

A  switch  is  provided  to  change  the  response  of  the 

stability  circuit  to  suit  different frame  size  generators  and 
applications. The table shows the options  available.
The  s lo w   response  s e ttin g s   m ay  p rove  h e lp fu l  in 
re d u c in g  lam p flic k e r.

The  correct  setting  of  the  Stability  adjustm ent  can  be 

found  by  running  the  generator  at  no  load  and  slowly 
turning  the  stability  control  anti-clockwise  until  the 

generator voltage starts to become unstable.

The  optimum  or  critically  damped  position  is  slightly 
clockwise  from  this  point  (i.e.  where  the  machine  volts 
are stable but dose to the unstable region).

UNDER  FREQUENCY ROLL OFF (UFRO) 

ADJUSTM ENT

The  AVR  incorporates  an  underspeed  protection  circuit 
which  gives  a  volts/Hz  characteristic when  the  generator 
speed  falls  below  a  presettable  threshold  known  as  the 
"knee" point.

The  red  Light  Emitting  Diode  (LED)  gives  indication  that 
the  UFRO circuit is operating.

The  UFRO  adjustment  is  preset  and  sealed  and  only 
requires the selection of 50/60Hz using the ju m per link.

For  optimum  setting,  the  LED  should  illuminate  as  the 

frequency  falls  just  below  nominal,  i.e.  47H z  on  a  50Hz 
system  or 57Hz on a 60Hz system.

DROOP ADJUSTMENT

Generators  intended  for  parallel  operation  are  fitted  with 
a  quadrature  droop  C.T.  which  provides  a  power  factor 
dependent  signal  for  the  AVR.  The  C.T.  is  connected  to 
S1,  S 2 o n  the AVR.

The  DROOP  adjustment  is  normally  preset  in  the  works 
to give 5%  voltage droop at full load zero power factor.

Clockwise  increases  the  amount  of  C.T.  signal  injected 
into the AVR  and  increases the droop with  lagging  power 
factor  (cos  0 ).  With  the  control  fully  anti-clockwise  there 
is  no droop.

TRIM AD JUSTM ENT

An  analogue  input  (А1  A2)  is  provided  to  connect  to  a 

Power  Factor  Controller  or other  devices.  It  is  designed  to 
accept dc signals  up to +/- 5 volts.

WARNING l  A n y  device s  conn e cte d   to   th is   in p u t  m ust 
be fu lly  flo a tin g  and  g a lva n ica lly  iso la te d  fro m   g round , 
w ith   an  in s u la tio n   c a p a b ility   o f  500  Vac. 

Failure  to 

obse rve th is  c o u ld  re s u lt in  e q u ip m e n t dam age.

The dc signal  applied to this  input adds to the AVR sensing 
circuit.  A1  is  connected to the AVR  0  volts.  Positive on A2 
increases excitation.  Negative on A2 decreases excitation.

The TRIM control  allows the user to adjust the sensitivity of 
the  input. 

W ith  TRIM  fully  anti-clockwise  the  externally 

applied  signal  has  no  effect.  Clockwise  it  has  maximum 
effect.

Normal  setting  is  fully  clockwise  when  used  with  a  Power 
Factor Controller.

OVER  EXCITATION (EXC TRIP) ADJUSTM ENT

The  adjustment  is  set  and  sealed  in  the  works  and  should 
not be altered.

An  over  excitation  condition  is  indicated  on  the  common 

LED  which also indicates  under speed running.

The  generator  must  be  stopped  to  reset  an  over  excitation 

condition.