background image

AS440 AUTOMATIC VOLTAGE 

REGULATOR (AVR)

SPECIFICATION  INSTALLATION AND ADJUSTMENTS

General  description

AS440  is  a  half wave  phase  controlled  thyristor  type  AVR 
and  forms  part  o f  the  excitation  system  for  a  brushless 

generator.  The  design employs  Surface  Mount Technology 
(SMT)  for  high  integration  of  features  in  a  small  footprint 

AVR.

Positive voltage  build up from  residual  levels  is  ensured by 
the  use of efficient semiconductors  in the  power circuitry of 
the  AVR.  The  power  and  voltage  sensing  circuits  have 
separate  terminals,  allowing  the  excitation  power  to  be 
derived  directly  from  the  stator  winding  for  basic 
applications  or from  an  auxiliary winding  if sustained  short 
circuit performance  is required.

The  AVR  is  linked  with  the  main  stator  windings  and  the 
exciter field  windings  to  provide  closed  loop  control  of  the 
output voltage with  load regulation of + / - 1.0%.

The  AVR  voltage  sensing  terminals  continuously  sample 
the  output  windings  for  voltage  control  purposes.  In 
response  to  this  sample  voltage,  the  AVR  controls  the 
power fed  to  the  exciter field,  and  hence  the  main  field,  to 
maintain  the  machine  output  voltage  within  the  specified 

limits,  compensating  for  load,  speed,  temperature  and 

power  factor,  ot the generator.

A frequency measuring circuit continually monitors the 
generator  output  and  provides  under-speed  protection  of 
the  excitation  system,  by  reducing  the  output  voltage 
proportionally with speed below a  pre-settable threshold.  A 
manual  adjustment  is  provided  for  factory  setting  of  the 
under frequency  roll  o ff  point,  (UFRO).  This  can  easily  be 
changed  to  50  or  60  Hz  in  the  field  by  push-on  link 
selection.

Over excitation  conditions  are  limited  to  a  safe  period .by  a 
protection circuit within the AVR.

Provision is  made for the connection of a remote voltage 

trimmer,  allowing  the  user  fine  control  of  the  generator’s 
output.

An  analogue  input  is  provided  allowing  connection  to  the 

Power  Factor  controller  or  other  external  devices  with 

compatible output.

The AVR  has  the  facility for droop  CT connection,  to  allow 
parallel  running with other similarly equipped generators.

Technical specification

SENSING  INPUT

Voltage

Jumper selectable 

100-130 V ac 1  phase or 
190-264 Vac  1  phase

Frequency

50-60 Hz nominal

POWER  INPUT

Voltage

100-264 V  ac 1  phase

Frequency

50-60 Hz nominal

OUTPUT

Voltage

82 V d.c. @ 200 V  a.c.

Current

continuous 4A (see note  1). 

transient 7.5A for 10 secs.

Resistance

15 ohms  min
(10 ohms min when input

volts is less than  175 ac)

REGULATION

+ / - 1.0%  (see note 2)

THERMAL DRIFT

0.03% per deg. С change in AVR ambient (see note 3) 

TYPICAL SYSTEM  RESPONSE

AVR  response 

20 ms

Filed current to 90% 

80 ms

Machine Volts to 97% 

300 ms

EXTERNAL VOLTAGE ADJUSTMENT

+/-10% with  1  к ohm  1  watt trimmer (see  note 4) 
Increasing resistance lowers voltage.

UNDER  FREQUENCY PROTECTION

Set point 

94 -93%  Hz (see r.o'.e 5)

UNIT POWER DISSIPATION 

12 watts maximum 

BUILD UP VOLTAGE

4 Volts @ AVR terminals 

ANALOGUE INPUT

Maximum input  +/- 5 Vdc (see note 6)
Sensitivity 

1V for 5% Generator Volts (adjustable) 

Input resistance  1k ohm 

QUADRATURE DROOP  INPUT 

10 ohms burden
Max.  sensitivity:  0.07 A  for 5% droop 0PF 
Max.  input:  0.33 A 

OVER EXCITATION PROTECTION

Set point 

Time delay 

ENVIRONMENTAL 

Vibration

75 V d c
10-15 seconds (fixed)

20-100 Hz 

1 0 0 H z -2 k H z  

Operating temperature 

Relative  Humidity 0-70C 
Storage temperature

50mm/sec

3.3g
-40 to +70C (note 7) 

95% (note 8)

-55 to +80C

NOTES
1. 

De-rate  by  12% if mounted  in 'portrait' orientation.

2. 

With 4% engine governing.

3. 

After 2 minutes.

4. 

Generator de-rate may apply. Check with factory.

5. 

Factory set, semi-sealed, jum per selectable.

6. 

Any device connected to the analogue input must be fully 
floating (galvanically isolated from ground), with an 
insulation  strength of 500V ac.

7. 

De-rate output current by 5% per degree С above 60C.

8. 

Non condensing.

1  / 4  Page