PlantLinc
PLR5000 User’s Guide
P/N 161-09888-001
DATA-LINC
Group
22
PLR5000 Front Panel LEDs
The LEDs on the PLR5000’s front panel provide important information the of the radio modems. Compare
the status of a radio modem’s LEDs with the tables below to aid you in the troubleshooting process
SR
Solid Red
FA
Flashing Amber
FY
Flashing Yellow
FG
Flashing Green
MG
Momentary Green
O
Off
SA
Solid Amber
Table 6: LED Status in Point-to-Point
P
=power
C
=carrier detect
I
=data in
O
=data out
Configuration
Master
Remote
Repeater
LED Indicators
P C I O
P C I O
P C I O
Powered, no RF
link
SR O O O
SR O O O
SR O O O
RF link
established
SR SA O O
SR SA O O
SR O O O
Data flow Master
to Remote
SR SA FY O
SR SA O FG
SR SA O O
Data Remote to
Master
SR SA O FG
SR SA FY O
SR SA O O
Configuration
mode
SR SA O MG
SR SA O MG
SR SA O MG
Data out LED lights
momentarily when the
configuration button
is depressed.
Table 7: LED Status in Point-to-Multipoint
P
=power
C
=carrier detect
I
=data in
O
=data out
Configuration
Master
Remote
Repeater
LED Indicators
P C I O
P C I O
P C I O
Powered, no RF
link
SR O O O
SR O O O
SR O O O
RF link
established
SR O O O
SR SA O O
SR O O O
Data flow Master
to Remote
SR FA FY O
SR SA O FG
SR SA O O
Data Remote to
Master
SR FA O FG
SR SA FY O
SR SA O O
Configuration
mode
SR FA O MG
SR SA O MG
SR SA O MG
Data out LED lights
momentarily when the
configuration button
is depressed.