40
used in a control circuit not exceeding 5 amps at 24 VAC. Use field supplied Class 1 wiring.
These programmable output contacts will close on a failure and remain closed until the alarm is no
longer present. The terminal designations for these alarm output contact pairs are:
Table 10 Remote Alarm Contacts Terminals
TB1
Function
15
Remote Alarm (Common)
14
Remote Alarm 1 (Normally Open)
16
Remote Alarm 1 (Normally Closed)
Remote Sensors
The Mini-dap4 panel comes with combination remote mounted temperature and humidity sensor for
field installation. The sensors are attached to standard 35 feet (11 m) of cable and come mounted in a
remote sensor enclosure. The temperature and humidity sensors require a total of four wires and the
provided cable is twisted, shielded type cable. Optional 50 feet (15 m) to 150 feet (46 m) length of
cables are available.
Condensate Pumps
The optional condensate pump normally requires a separate source of 110-volt power. Always check
the pump power requirements before connecting power. Condensate pumps are available in other
voltages.
When a condensate pump needs to be mounted outside of the cabinet of the unit, mount the provided
pump to the side of the unit or some other support near the unit. The pump will need to be lower than
the drain pan in the unit. A P-trap will need to be field installed between the drain and the pump to allow
proper drainage of the condensate water into the pump. See section
Disconnect Switch (Optional)
A thru door locking disconnect switch is an optional feature which includes a non-automatic disconnect
switch mounted in the high voltage section of the electrical control box. The operating mechanism
prevents access to the high voltage electrical components until switched to the "OFF" position. The
operating mechanism protrudes through the exterior door and is lockable in the OFF position.
NOTICE:
The optional disconnect switch extension shaft and locking handle
are shipped loose to prevent damage during transit and installation. It is the
installing contactors responsibility to install these components as part of the
installation process.
Содержание DAMA-01
Страница 1: ......
Страница 82: ...MiniCeiling_IOM 10 2022...