Oilburner
Type Gulliver RG3D
Page 8 of 10
Adjustment
[K:\framen\instrukt\Dantherm\RG\Engelsk\RG3D\RG3.fm-021114-dm/lbk]
2nd stage adjustment:
Adjustment of air shutter:
Unloosen the nut (4), turn the screw (5) until he in-
dicator (3) reaches the position desired. Then lock
the nut (4).
Pressure:
This is set at 15 bar at the factory.
Should it be necessary to re-set or alter such
pressure, this can be done, by adjusting screw
(9). The pressure gauge must be mounted in pla-
ce of cap (8).
When burner shuts down the air damper automai-
cally closes till a max. chimney depressure of
0,5 bar.
1st stage adjustment
Adjustment of air shutter:
Unloosen the nut (1), turn the screw (2) until
the indicator (3) reaches the position desired.
Then lock the nut (1).
Pressure regulation:
This is set at 9 bar at the factory.
Should it be necessary to re-set or alter such
pressure, this can be done, by adjusting screw
(7).
The pressure gauge must be mounted in place
of cap (8).