 °Dantherm Air Handling A/S., Skive, 7800 DENMARK 

 Controller - CC4   SW Ver - 0.4e 

 ----------------------------------------------------------- 

 CC4 Configuration SW 2013.02.11 

 ----------------------------------------------------------- 

 Device: Flexibox 810, 368453 

 ----------------------------------------------------------- 

 Cooling Fan Configuration 

                                      Fan 1    Fan 2      Fan 3 

 

 1.OFF Temp                  [xT0][-40-80]: 20.0    :0.0     :20.0 

 2.IDLE ON Temp              [xT1][-40-80]: 24.0    :5.0     :25.0 

 3.IDLE entry Temp           [xT2][-40-80]: 24.0    :22.0     :30.0 

 4.SET POINT Temp            [xTs][-40-80]: 24.0    :24.0     :30.0 

 5.HIGH SPEED Temp           [xT3][-40-80]: 28.0    :30.0     :55.0 

 6.EXTND HS entry Temp       [xT4][-40-80]: 30.0    :34.0     :55.0 

 7.EXTND HS exit Temp        [xT5][-40-80]: 28.0    :32.0     :55.0 

 8.BOOST entry Temp          [xT6][-40-80]: 36.0    :40.0     :60.0 

 9.BOOST exit Temp           [xT7][-40-80]: 34.0    :35.0     :55.0 

 

 10.IDLE_RPM               [xR1][500-9999]: 500      :1000        :800 

 11.HIGH SPEED RPM         [xR3][500-9999]: 1860      :1700        :1400 

 12.EXTND HS RPM           [xR2][500-9999]: 2000      :1300        :1600 

 13.IDLE Duty Cycle          [xD1][10-100]: 20       :20        :30 

 14.HIGH SPEED Duty Cycle    [xD3][10-100]: 80       :80        :80 

 15.EXTND HS Duty Cycle      [xD2][10-100]: 65       :65        :80 

 16.BOOST Duty Cycle         [xD4][10-100]: 100       :100        :100 

 17.Dead Band RPMCycle     [DBx][100-1000]: 100       :100        :100 

 

 18.Override - Digi.1            [x/0/1]: 0       :x        :x 

 19.Override - Digi.2            [x/0/1]: 0       :x        :x 

 20.Override - Sensor Fail       [x/0/1]: x       :x        :x 

 21.Sens.Sel. OBD/ROOM/SUPP/COND [0/1/2/3]: 1       :1        :3 

 22.Tacho pulse/rev             [Tpx][1-8]: 3       :3        :3 

 23.Tacho Control Ena/Dis       [Tcx][0/1]: 0       :0        :1 

 24.Ctrl type [0-10V/PWM]       [Ctx][0/1]: 0       :0        :0 

 25.Enable                      [xFe][0/1]: 1       :0        :0 

 

 

 ----------------------------------------------------------- 

 Damper Configuration 

                                      Damper 1     Damper 2 

 

 1.LOWER Close Temp        [dT0][-40-80]: 20.0  : 20.0 

 2.SET POINT               [dTs][-40-80]: 24.0  : 24.0 

 3.UPPER Open Temp         [dT1][-40-80]: 60.0  : 60.0 

 4.UPPER Close Temp        [dT2][-40-80]: 60.0  : 60.0 

 5.EMGNCY Open Temp        [dT3][-40-80]: 60.0  : 60.0 

 

 6.Override - Digi.1             [x/0/1]: 0     : 0 

 7.Override - Digi.2             [x/0/1]: 0     : 0 

 8.Override - Sensor Fail        [x/0/1]: x     : x 

 9.Sensor Sel. OBD/ROOM/SUPPLY   [0/1/2]: 1     : 1 

 10.Damper Run dur.           [30 - 300]: 120     : 120 

 11.Enable                    [xDè][0/1]: 1     : 0 

 

 

 ----------------------------------------------------------- 

 Compressor/AC-Unit Configuration 

                                      Comp     A/C 1     A/C 2 

 

 1.ON Temp                     [cT0][-40-80]: 32.0  : 32.0  : 32.0 

 2.OFF Temp                    [cT1][-40-80]: 30.0  : 30.0  : 30.0 

 

 3.Emerg ON Temp               [cT2][-40-80]: 55.0  : 36.0  : 36.0 

 4.Emerg OFF Temp              [cT3][-40-80]: 55.0  : 34.0  : 34.0 

 

 5.Override - Digi.1                 [x/0/1]: x     : 0     : 0 

 6.Override - Digi.2                 [x/0/1]: x     : x     : x 

 7.Override - Sensor Fail            [x/0/1]: x     : x     : x 

 8.Sensor Sel. OBD/ROOM/SUPPLY       [0/1/2]: 1     : 1     : 1 

 9.Min. ON duration Sec.(1-30min)  [60-1800]: 480     : 180     : 180 

 10.Restart time-out Sec.(1-30min) [60-1800]: 120     : 180     : 180 

 11.Lead/Lag Enable                    [0/1]: 0     : 0     : 0 

 12.Enable                        [xAe][0/1]: 0     : 0     : 0 

 

 

 ----------------------------------------------------------- 

 Heater Configuration 

 

 1.ON Temp                 [hT0][-40-80]: 12.0 

 2.OFF Temp                [hT1][-40-80]: 14.0 

 

 3.Override - Digi.1             [x/0/1]: 0 

 4.Override - Digi.2             [x/0/1]: 0 

 5.Override - Sensor Fail        [x/0/1]: x 

 6.Sensor Sel. OBD/ROOM/SUPPLY   [0/1/2]: 1 

 7.Enable                     [xDe][0/1]: 1 

 

 

 ----------------------------------------------------------- 

 

System Control Configurations 

 

 

 1.Norm. Vdc Low Level       [V1][18-60]: 40 

 2.Norm. Vdc High Level      [V2][18-60]: 60 

 3.Temp Alarm Low Limit   [TL][(-40)-80]: 0.0 

 4.Temp Alarm high Limit  [TH][(-40)-80]: 50.0 

 5.Delta T                [Dt][(-40)-80]: 3.0 

 6.Alarm1 NO/NC Type         [Àlm1][0/1]: 0 

 7.Alarm2 NO/NC Type         [Alm2][0/1]: 0 

 8.Alarm1 delay sec  [Alm1 delay][0-100]: 10 

 9.Alarm2 delay sec  [Alm2 delay][0-100]: 10 

 10.Dig.1 NO/NC Type          [Dig1][0/1]: 0 

 11.Dig.2 NO/NC Type         [Dig2][0/1]: 0 

 12.Door Xtch. NO/NC Type    [Door][0/1]: 0 

 13.Filter Grd NO/NC Type    [Filt][0/1]: 0 

 14.Phase Monitor NO/NC Type  [PHm][0/1]: 0 

 15.Status Log Dis/Ena.       [Log][0/1]: 1 

 16.Log interval in min.     [Int][1-60]: 1 

 17.RS-485 Bus Pow. Dis/Ena        [0/1]: 1 

 18.ModBus Slave Addr            [1-255]: 23 

 

 19.Alarm Mapping             1.Alarm1  2.Alarm2 

   1.Pwr Save Mode [PSM][0/1]:   1       :  0 

   2.Room Temp H/L [THL][0/1]:   1       :  0 

   3.Fan 1          [F1][0/1]:   1       :  0 

   4.Fan 2          [F2][0/1]:   0       :  0 

   5.Fan 3          [F3][0/1]:   0       :  0 

   6.Onbrd. Sens    [OS][0/1]:   0       :  0 

   7.Room Sens      [RS][0/1]:   1       :  0 

   8.Amb.  Sens     [AS][0/1]:   1       :  0 

   9.Supp. Sens     [SS][0/1]:   0       :  0 

   10.Cond.  Sens   [CS][0/1]:   0       :  0 

   11.Digi.1 I/P   [FIL][0/1]:   0       :  0 

   12.Digi.2 I/P    [FI][0/1]:   0       :  0 

   13.Door Xtch I/P [DI][0/1]:   0       :  0 

   14.Filt Grd I/P  [FI][0/1]:   0       :  1 

   15.Phase I/P     [FI][0/1]:   0       :  0 

 

 

Содержание Flexibox 460

Страница 1: ...Flexibox 460 810 Quick setup guide Rev 1 1...

Страница 2: ...the installation method and installation orienta tion Not following these instructions could result in injury death or damage to equipment All work should be performed by qualified personal using safe...

Страница 3: ...3 1x 1x 1x 2x 1x 1x 5 mm 8 mm 4 mm 3 mm 2 mm Tools needed...

Страница 4: ...dimension 460 810 455 mm 18 inch 472 mm 18 6 inch 758 mm 29 9 inch 500 mm 19 7 inch 503 mm 19 7 inch Product overview indoor view Earth connection Main PCB with connections Incoming air flow Incoming...

Страница 5: ...w Exploded Intregreted rainhood fan controller Filter Filter lock Airflow outside air inlet Shelter air supply Safety grill front Installation bracket 460 versus 810 Flexibox 460 Flexibox 810 100mm 85...

Страница 6: ...6 Prepare unit Cut hole minimum 900mm 35 5 inch 225 mm 8 9 inch 430 mm 17 inch 1 40mm 3 2 8 mm 4 mm 3 mm 8 mm 4 mm 3 mm Warning Caution...

Страница 7: ...7 Mount bracket Mount unit Center 8 mm 4 mm 3 mm 2x 2x 8 mm 4 mm 3 mm 1 3 2 3 3 3 10mm 10mm 2x...

Страница 8: ...8 Seal unit Mount damper Flexibox dampers Quick setup guide Rev 1 0...

Страница 9: ...9 Mount indoor sensor Connect earth Keep clear To shelter earth...

Страница 10: ...48V DC positive 48V DC 16A fused 2 5 mm2 wires AWG 13 External safety breaker 0 0 0 3x0 75 mm AWG 18 Belimo LM72 4 5 4 1 4 5 4 3 4 5 4 2 NOT included NOT included 1m 3x0 75 mm White Black 1 2 4 5 4 3...

Страница 11: ...11 Mount display accessory 2x 8 mm 4 mm 3 mm...

Страница 12: ...rnal aircon OFF Lead Lag Not active Mode Idle Menu item up Select item Menu item down menu item Step value up Store and return Step value down 28 C CC4 Flexibox 29 C Type Cooling setpoint Room tempera...

Страница 13: ...ur 30 300 120 120 11 Enable xD 0 1 1 0 Compressor AC Unit Configuration Comp A C 1 A C 2 1 ON Temp cT0 40 80 32 0 32 0 32 0 2 OFF Temp cT1 40 80 30 0 30 0 30 0 3 Emerg ON Temp cT2 40 80 55 0 36 0 36 0...

Страница 14: ...Alarm 1 Alarm 1 AC 1 AC 1 Ext damper GND Ext damper close Ext damper open SD reader 48V DC negative 48V DC positive 48VDC 16A fused 2 5 mm External safety breaker not included t 0 12V DC with pull up...

Страница 15: ...ax 0 121 133 70 infose dantherm com www dantherm se Dantherm Limited 12 Windmill Business Park Windmill Road Clevedon North Somerset BS21 6SR England Phone 44 0 1275 87 68 51 Fax 44 0 1275 34 30 86 in...

Страница 16: ...Dantherm Air Handling A S Marienlystvej 65 7800 Skive Danmark www dantherm com service dantherm com 076213 076213...

Отзывы: