28
Example from Elite 400.
Setting the air volume and temperature
The control PCB has dipswitches for regulation of the fan
speed.
By means of the dipswitches 1 – 6 you can choose between
8 different fan speeds.
By means of the dipswitches 7 – 8 you can choose between
4 different supply air temperatures.
Setting the temperature
Table 1.
Supply air
temperature Setting of
dipswitches
7 8
On
8°C
Off
On
17°C
Off
On
19°C
Off
On
21°C
Off
NOTE: Observe local power supply regulations.
Earth (yellow and green) -
Neutral (blue) - N
Phase (black or brown) - L
NOTE: Standard temperature is pre-set at 21
o
C.
NOTE: The setting of dipswitches at 8
o
C is intended
for frost protection of the water heating coil.
The water heating coil is an optional.
Table 1 shows the combination possibilities for
adjusting the most suitable supply air temperature
for the given situation
Table 1 shows the setting of dipswitches 7 – 8.