Electrical connections

This below illustration shows the pin assignment for connections:

J1

J5

J9

J4

J16

J17

J6

J11

J10

J15

J7

J3

J2

AL 1

AL 2

AC 1

AC 2

RS485 in

RS485 out

TTL

1=Gnd

2=B

3=Gnd

4=A

5-8=nc

1=Gnd

2=B

3=Gnd

4=A

5-6=line pwr gnd

7-8=12v line pwr

PC interface - galvanic isolated

Gnd
Room sensor
Gnd
Digital input 2
Gnd
Digital input 1
Alarm 2
Alarm 2
Alarm 1
Alarm 1

AC 2
AC 2
AC 1
AC 1

Damper 2 GND
Damper 2 close
Damper 2 open

SD reader

48V DC negative

48V DC positive

48VDC
16A fused 

External safety breaker 

(not included)

-t°

Pre wired 

See unit schematics

Comp. out 1

Comp GND

Damper 1 open

Damper 1 close

Damper 1 GND

Heater out +

Heater out GND

Condenser fan out +

Condenser out GND

Amb temp sens

Amb temp sens GND

Supply temp sens

Supply temp sens GND 

Condenser temp sens

Condenser temp sens GND

Phase monitor input

Phase monitor input GND

Filter guard input

Filter guard input GND 

Door switch input

Door switch GND

1: Fan positive
2:Fan PWM
3:Fan tacho
4:Fan GND

1: Fan positive
2:Fan PWM
3:Fan tacho
4:Fan GND

1: Fan positive
2:Fan PWM
3:Fan tacho
4:Fan GND

Standard shielded ethernet cable 

(568A termination both ends)

Accessory

10A Mini blade terminal.

FX ”Littlefuse”  type ”997 010”

10A Mini blade terminal.

FX ”Littlefuse”  type ”997 010”

10A Mini blade terminal.

FX ”Littlefuse”  type ”997 010”

SD card slot for setup and logging

Green LED

Red LED

F2

F3

F4

0 / 12V DC with pull up

Potential free -max. 42VAc or 60VDc. / 

500mA - (SELV)-Default normally open - 

jumper changeable

48V DC/100mA

SD card slot for setup and logging

PC interface - galvanic isolated

48VDC

16A fused 

Green LED

Red LED

Accessory

Standard shielded ethernet cable 

 (568A termination both ends)

48V DC negative

External safety breaker   

(not included)

48V DC positive

Fig. 14 

External 
connections 

088013 • 

Version 1.0 • 30.01.2015 

en

17

Содержание Combo Cooling 6000/900

Страница 1: ...Combo Cooling 6000 900 Service manual Rev 1 0 en...

Страница 2: ...n accept no responsibility for possible errors and changes Irrt mer und nderungen vorbehalten Dantherm n assume aucune responsabilit pour erreurs et modifications ventuelles Dantherm no asume ninguna...

Страница 3: ...ion from Dantherm A S Dantherm reserves the right to make changes and improvements to the product and the service manual at any time without prior notice or obligation This service manual covers the f...

Страница 4: ...stallation method and installation orientation Not following these instructions could result in injury death or damage to equip ment All work should be performed by qualified personal using safe work...

Страница 5: ...s removes dissipated heat from electronic equipment and it s designed to maintain correct temperature for electronic equipment Dantherm recommends that the cooling system should be running continuousl...

Страница 6: ...view 1 2 5 4 3 Fig 1 This table refers to the outdoor view above Pos Description 1 Free cooling air inlet 2 Condenser cooling air output 3 Front door with lock 4 Removable side cover for service acces...

Страница 7: ...Fig 2 This table refers to the outdoor view above Pos Description 1 Free cooling supply air inlet 2 Return air 3 Cable routing option 1 4 Cable routing option 2 5 Removable installation bracket 6 Cond...

Страница 8: ...s table refers to the parts view above Pos Descriptions 1 Free cooling fan 2 Wall bracket frame 3 Embedded controller type CC4 4 Free cooling filter 5 AC free cooling operation shift damper 6 Cable ro...

Страница 9: ...led closed loop without cooling Air paths Free cooling Active cooling Circulation Fig 4 Warm internal air is drawn into the unit by the internal evaporator fan at the evaporator opening through the ev...

Страница 10: ...s designed to maintain cor rect and steady temperature for the electronic radio equipment The ComboCooler has both free cooling as well as AC cooling thus still having connection for additional exter...

Страница 11: ...numbers are product specific See more in unit manual Follow the display leaflet for guidance for usage of the display The controller has an integrated SD card reader that can exchange parameters for i...

Страница 12: ...devices NEVER lift the unit by hands use only forklift or similar hoisting device Unpack and prepare unit for mounting Step Action Illustration 1 Remove both side panels 1 Lift side 2 Pull outwards 3...

Страница 13: ...0 mm Fig 6 Please make sure that one of the two shown cable run options is achievable Standard option needs drilling holes in wall in center to the units holes Alternative option route the cable in fr...

Страница 14: ...r drilling the correct amount of cable inlets min 925 mm optimum 1125 mm or more 500 mm 323 mm 275 mm min 90 mm 800 mm 800 mm 364 mm 25 mm 30 mm 30 mm Drill only cable inlet if needed Fig 8 Fasten the...

Страница 15: ...a forklift or similar lifting device 4x DIN 10 Fig 10 Mount the four bolts securing the unit to the frame and seal the edges between unit and wall according illustration 4x DIN 10 Fig 11 Mounting uni...

Страница 16: ...e wants to be controlled Please make sure the sensor isn t blocked or touching any metal and isn t placed in the air stream coming from the ComboCooler Fig 12 Please pull cables from inside through wa...

Страница 17: ...included t Standard shielded ethernet cable 568A termination both ends Accessory 10A Mini blade terminal FX Littlefuse type 997 010 10A Mini blade terminal FX Littlefuse type 997 010 10A Mini blade t...

Страница 18: ...force a specific operation for instance shutting down the cooling system and close the damper in case of a fire J5 alarm 1 2 outputs Dry contact rated 0 5A 60Vdc Normally Open or Normally closed jump...

Страница 19: ...Room Sens RS 0 1 1 0 8 Amb Sens AS 0 1 1 0 9 Supp Sens SS 0 1 0 0 10 Cond Sens CS 0 1 0 0 11 Digi 1 I P FIL 0 1 0 0 12 Digi 2 I P FI 0 1 0 0 13 Door Xtch I P DI 0 1 0 0 14 Filt Grd I P FI 0 1 0 1 15...

Страница 20: ...n off Force external AC on off In all configuration menu sections the digital input functionality is controllable Cooling Fan Configuration Fan 1 Fan 2 Fan 3 18 Override Digi 1 x 0 100 0 x x 19 Overri...

Страница 21: ...nc jumper Be displayed on any connected RS 485 display Be logged on the SD card if available in the SD card reader when alarm is present This table shows the error according the shown E code Code Err...

Страница 22: ...it is located in bad quality air environment A written log at site is adequate documentation for preventive maintenance Switch off AC and DC supply before working on the unit Make sure that all work h...

Страница 23: ...Fig 15 The unit must be cleaned according to the recommended preventive maintenance plan Tools required Vacuum cleaner or compressed air Soft brush TX20 screwdriver AC cleaning agent if it s very dir...

Страница 24: ...s of leakage 3 Are the coil lamellas clean and undamaged 4 Are all fan blades free of any obstructions cracks or missing blades 5 When rotating the fans with the fingers do the fans rotate freely with...

Страница 25: ...ue N 2 Damper Supply 3 Damper Supply 1 Damper GND A2 A1 N L Gnd PWM Tacho Postive Gnd PWM Tacho Postive Comp control Comp control Filter Ambient temp Sensor Condensor fan Sensor HP LP Heater Heater He...

Страница 26: ...2 3 Pos Description Order no 1 Evaporator fan 012848 2 CC4 controller 075255 3 Damper motor 48V DC 075254 4 Condenser fan 230V AC EC type 075250 5 Compressor 1 phase 230V AC 50Hz 220470 na RS 485 exte...

Страница 27: ...55 Refrigerant amount Kg R410a 2 3 Expected service life 10 years Cooling capacity operational data 230V 50Hz Cooling capacity at 27 C internal and 35 C ambient sensible W 7115 Free cooling capacity 4...

Страница 28: ...cation Voltage 230V 50Hz 48V DC Circuit Breaker 16A 16A Wire Size 2 5mm2 12AWG 2 5mm2 12AWG These illustrations shows the units dimensions in millimetres 1997 527 1072 1055 370 500 323 246 888 57 601...

Страница 29: ...llustrations shows the units dimensions in inch 78 70 20 75 42 22 41 57 14 57 19 69 12 74 9 71 34 97 2 24 23 67 4 41 3 94 3 53 13 59 34 18 41 87 31 51 3 94 4 04 2 06 3 54 Fig 17 Dimensions in Inch 088...

Страница 30: ...he following standards EN ISO 12100 1 Machine safety EN 60 950 1 Electrical machinery safety EN 60 335 1 Low voltage EN 60 335 2 40 Low voltage particular requirements for electrical heat pumps air co...

Страница 31: ...N tter y 3101 T nsberg Phone 47 33 35 16 00 Fax 47 33 38 51 91 dantherm no dantherm com www dantherm com NO 918 348 328 MVA USA Dantherm Air Handling Inc 110 Corporate Drive Suite K Spartanburg SC 293...

Страница 32: ...Dantherm Air Handling A S Marienlystvej 65 7800 Skive Denmark www dantherm com service dantherm com 088013 088013...

Отзывы: