Error messages
An overview of possible errors which prevent normal operation
Error message
Illustra-
tion
Cause
Remedy
CDT 30-40-60:
Yellow light on
centre LED with
emptying symbol
and FULL on display
Water container is full
or fault on water
pump (accessory)
See emptying guide below, or
check pump outlet
Red light on right
warning LED HIGH
TEMP on display
Pressure or tempera-
ture in high pressure
element too high
Check filter and dehumidifier
for dirt in airways
Red light on right
warning LED AMBI-
ENT TEMP on
display
Room temperature out
of normal range
Place the dehumidifier in the
specified temperature range,
between 3°-32°C
Red light on right
warning LED SEN-
SOR FAIL on
display. One of the
internal sensors is
defective. Use the
+/- keys to toggle
between 3 possible
errors
SENSOR FAIL
1: EVAP FAIL
Evaporator
thermometer defective
Requires an authorised service
technician
2: COND FAIL
Condenser
thermometer defective
Requires an authorised service
technician
3: ROOM FAIL The
internal room
thermometer is
defective
Requires an authorised service
technician
Red light on right
warning LED LP
STOP on display
Leak in cooling circuit Requires an authorised service
technician
Continued on next page