4.3  Defrosting 

 
If the temperature falls to below 20ºC the evaporator may start to ice up after a short time.  
 
The defrosting function is activated when the evaporator sensor registers a temperature lower than 5ºC, after which 
the control will let the unit operate in dehumidification mode for another 30 minutes. Then the compressor is 
stopped and the unit switches over to active defrosting, which means that the cooling circuit turns and the hot 
refrigerant runs through the evaporator coil and melts the ice. When the evaporator sensor registers that the 
temperature is above 5ºC, the compressor starts again. 
 

 
4.4  Safety circuit 

 
If the temperature in the dehumidifier increases to a temperature of more than 55ºC (for example in case of fan 
failure), the compressor stops automatically to avoid damaging it. After 45 minutes the compressor starts again 
automatically. 
 
By room temperatures outside the unit’s working range (3 - 32°C) it is automatically switched off to protect the 
evaporator coil from icing up and the condenser coil from overheating. The unit will automatically start again when 
the room temperature is within the working range. 
 
 

4.5  Compressor control 

 
The number of compressor starting is limited by a 6 minutes timer, which starts up when switching on the 
compressor. The timer must have come to an end before the compressor can be switched on again.  
 
Each time the unit has been switched off on the main switch, by the built-in hygrostat, or by an external hygrostat, 
it will take 30 seconds before the unit can be switched on again. This is a safety function protecting the compressor 
against overloading caused by too high pressure in the cooling circuit at start up. 

 

5.  Maintenance 

 
The dehumidifier requires very little attention for trouble free running. All the necessary safety and control 
functions have been built in. The fan motor and the compressor have permanent lubrication and require no 
particular maintenance. 
 
 

5.1 Cleaning of filter 

 
Once a month the air inlet filter should be checked and cleaned if necessary. The front cover panel is removed and 
the filter taken out. Clean the filter in tepid soapy water or if not badly soiled by vacuum cleaning. 
 
 

NOTE!  If the air humidity is below 50%RH, the unit will not 

start when the power is connected. 

   

Содержание CDF 10

Страница 1: ...GES 8 13 DEUTSCH SEITE 14 20 FRANCAIS PAGES 21 27 Der tages forbehold for trykfejl og ndringer Dantherm can accept no responsibility for possible errors and changes Irrt mer und nderungen vorbehalten...

Страница 2: ...control 10 3 Connection of power supply 11 4 Operation 11 4 1 LED indication Switch 11 4 2 Built in hygrostat 11 4 3 Defrosting 12 4 4 Safety circuit 12 4 5 Compressor control 12 5 Maintenance 12 5 1...

Страница 3: ...ng turned into heat energy more heat is returned to the air than was previously extracted This extra heat corresponds to an approximate increase in temperature of 5 C The repeated circulation of air t...

Страница 4: ...le a radiator and doors and windows must be kept closed when the dehumidifier is in function 2 2 Condensate outlet The condensate outlet is located at the bottom of the dehumidifier The unit has a dra...

Страница 5: ...it dehumidifies The dehumidifier is switched on and off by the switch on the side 4 2 Built in hygrostat The dehumidifier is controlled by a built in hygrostat that is set to approx 50 RH When the hyg...

Страница 6: ...rom overheating The unit will automatically start again when the room temperature is within the working range 4 5 Compressor control The number of compressor starting is limited by a 6 minutes timer w...

Страница 7: ...erwards check the following 5 Check that the fan is running when the unit starts after 45 minutes 6 Check whether the condensor coil is dirty 7 Check whether the filter is dirty 8 Check whether the ro...

Страница 8: ...vaporator Verdampfer vaporateur 3 Luftk let kondensator air cooled condensor luftgek hlter Kondensator condenseur air 4 Kapillarr r capillary tube Kapillarrohr tubes capillaires 5 T rfilter liquid lin...

Страница 9: ...29 8 El diagram Wiring diagram Schaltplan Sch ma lectrique CDF 10 1 x 230V 50Hz...

Страница 10: ...Designation Beschreibung D signation TS1 Kondensatorf ler Condenser sensor Kondensatorf hler Sonde du condenseur TS1 Fordamperf ler Evaporator sensor Verdampferf hler Sonde d vaporateur M2 Ventilator...

Страница 11: ...31 CDF 10 1 x 230V 50Hz...

Страница 12: ...teur basculant 18 084751 19 600990 Kondensatorflade Condensor Kondensator Condenseur 20 084752 21 516350 Hygrostat Hygrostat Hygrostat Hygrostat 22 293646 Holder for hygrostat Retainer for hygrostat H...

Страница 13: ...33...

Страница 14: ...34...

Страница 15: ...35...

Страница 16: ...36...

Отзывы: