►►►6. ALARM LIST
ALARM
POSSIBLE CAUSE
POSSIBLE SOLUTION
FULL + “FULL“
Full or missing tank
The alarm is automatically reset by empty-
ing or inserting the tank
ALARM + “Lo t“
Room temperature too
low
Room temperature conditions not suitable
for operation
ALARM + “Prob“
Malfunction of the humid-
ity probe. In any case, the
unit continues to operate
Contact the authorised service centre
ALARM + “Pro2“
Malfunction of the ambi-
ent temperature probe
Contact the authorised service centre
ALARM + “dEFr“
ALARM + “Lotd”
Defrosting thermostat
malfunction
Contact the authorised service centre
ALARM + “HiPS“
High pressure alarm in
the refrigerant circuit
Clean both the air filters.
Disconnect the unit from the power supply.
Open the electrical panel and reset the
high pressure switch.
If the alarm persist contact the authorised
service centre
ALARM + “LoPS“
Low pressure alarm in the
refrigerant circuit
Clean both the air filters.
Disconnect the unit from the power supply
and riconnect.
If the alarm persist contact the authorised
service centre