background image

P

AGE

 4

46032-05-0199 <90-00146>

INSTALLATION

I

nstall the module in the proper slot in the shelf. The shelf is

 normally pre-wired at the factory. If necessary, refer to Figs. 1

and 2 and Table A for edge connector pin designations.

F

IG

. 2 - E

DGE

 C

ONNECTOR

 P

IN

 D

ESIGNATION

, 46032-05

56

55

54

53

52

51

50

49

48

47

46

45

44

43

42

41

40

39

38

37

36

35

34

33

32

31

30

29

28

27

26

25

24

23

22

21

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

CIRCUIT SIDE
OF PC BOARD

COMPONENT SIDE

OF PC BOARD

K15

K16

K13

K14

K11

K12

K9

K10

K7

K8

K5

K6

K3

K4

K1

K2

-Battery

K16A

K16B

K15A

K15B

K14A

K14B

K13A

K13B

K12A

K12B

K11A

K11B

K10A

K10B

K9A

K9B

+Ground

K8A

K8B

K7A

K7B

K6A

K6B

K5A

K5B

K4A

K4B

K3A

K3B

K2A

K2B

K1A

K1B

Operating

Inputs

All relay

outputs are

normally-open

Содержание 46032-05

Страница 1: ...afety precautions refer to BellcoreTM Technical Reference TR NWT 000870 Copyright 1999 by Dantel Inc Dantel is a registered trademark of Dantel Inc ISO 9001 Registered Printed in the U S A INSTALLATION OPERATION MANUAL 46032 05 0199 90 00146 46032 05 RELAY MODULE About this Practice This practice has been reissued to Meet ISO 9001 requirements Issue date January 1999 Reissued Practices Updated and...

Страница 2: ...operations Each relay is operated by the presence of 5VDC The front panel provides 16 LED indicators to visually monitor the internal relay activity This module operates on 21 to 56 VDC input power CIRCUIT DESCRIPTION The 46032 05 Relay Module functional schematic is shown in Fig 1 Refer to Table A for the individual relay pin outs Relays K1 through K16 have Form A normally open contacts which pro...

Страница 3: ...BER 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Battery Ground RELAY COIL C 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 35 17 CONTACT A 1 3 5 7 9 11 13 15 19 21 23 25 27 29 31 33 CONTACT B 2 4 6 8 10 12 14 16 20 22 24 26 28 30 32 34 CIRCUIT DESCRIPTION FIG 1 FUNCTIONAL SCHEMATIC 46032 05 RELAY MODULE TABLE A PC PIN NUMBER 46032 05 RELAY MODULE ...

Страница 4: ... 55 54 53 52 51 50 49 48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 CIRCUIT SIDE OF PC BOARD COMPONENT SIDE OF PC BOARD K15 K16 K13 K14 K11 K12 K9 K10 K7 K8 K5 K6 K3 K4 K1 K2 Battery K16A K16B K15A K15B K14A K14B K13A K13B K12A K12B K11A K11B K10A K10B K9A K9B Ground K8A K8B K7A K7B K6A K6B K5A K5B K4A K4B K3A...

Страница 5: ...CATIONS DESCRIPTION Input Voltage Range Current Requirements No relays Operating One Relay Enabled All Relays Enabled Heat Dissipation One Relay Enabled All Relays Enabled Relay Contacts Current Rating Resistance Operating Temperature Physical Dimensions Weight DESCRIPTION 21 to 56 VDC 21VDC 24 VDC 48 VDC 56 VDC 0 0 mA 0 0 mA 0 0 mA 0 0 mA 7 4 mA 8 4 mA 10 4 mA 11 6 mA 118 0 mA 134 0 mA 172 8 mA 1...

Страница 6: ...ten instrument signed by a duly authorized officer of the Seller and accepted by the Buyer Warranty and remedies on products not manufactured by the Seller are in accordance with warranty of the respective manufacturer THE SELLER MAKES NO OTHER WARRANTY OF ANY KIND WHATSOEVER EXPRESSED OR IMPLIED AND ALL IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PUR POSE WHICH EXCEEDS THE AFORESAID OBLIGATIONS ...

Отзывы: