46023-12-0399 <90-00009>

 P

AGE

 5

INSTALLATION

1. P

ORT

 T

ERMINATION

You can strap the 46023-12 MAC to have its alarm inputs (receive

lines) either terminated or unterminated.  The terminating load is

100 ohms.  Each alarm port must have a current path at some

point of termination, which is normally set at the MAC.

Thru-Hole Version

If a channel is connected to communications lines, the resistor

is normally strapped IN (position 1-2).

If termination for a channel is provided at the source, strap the

resistor OUT.

Refer to Table A and Fig. 2.

T

ABLE

 A - R

ECEIVE

 L

INE

 T

ERMINATION

 (T

HRU

-H

OLE

 V

ERSION

)

F

IG

. 2 - S

WITCH

 

AND

 S

TRAP

 O

PTION

 L

OCATIONS

 (T

HRU

-H

OLE

 V

ERSION

)

ALARM PORT

NUMBER

1

2

3
4

5

6
7

8

STRAP

NUMBER

X1

X2

X3
X4

X5

X6
X7

X8

1

S 1

2 3 4 5 6 7 8

1

S 2

2 3 4 5 6 7 8

UP  IS  OFF

UP  IS  OFF

3   2   1

IN

OUT

X8
X7
X6
X5
X4
X3
X2
X1

NOTE:

Switch S2 is not used.

UPDATED

Содержание 46023-12

Страница 1: ...charge safety precautions refer to BellcoreTM Technical Reference TR NWT 000870 Copyright 1999 by Dantel Inc Dantel is a registered trademark of Dantel Inc ISO 9001 Registered Printed in the U S A INS...

Страница 2: ...one is a 46023 12 Smart MAC all the others must be 46023 12 Smart MACs as well You cannot use the 46023 12 Smart MAC in combination with 46022 12 20 or 30 MACs Here are some features of the 46023 Sma...

Страница 3: ...d through RS 422 drivers and receivers The receive lines have an optional strap selection for 100 ohm termination The configuration of the MAP determines the data rate and proto col of each port The m...

Страница 4: ...ACE 51 54 53 42 45 44 43 36 56 55 50 45 49 47 POWER SUPPLY SUBASSEMBLY 17 35 DISPLAY DRIVER FRONT PANEL LEDs AND SWITCHES CARD SELECT CHANNEL SELECT DISPLAY CONTROL TO MATs CPMs ETC PORT 2 TX RX TX RX...

Страница 5: ...n If a channel is connected to communications lines the resistor is normally strapped IN position 1 2 If termination for a channel is provided at the source strap the resistor OUT Refer to Table A and...

Страница 6: ...source switch the resistor OFF Refer to Table B and Fig 3 TABLE B RECEIVE LINE TERMINATION SMT VERSION FIG 3 SWITCH AND STRAP OPTION LOCATIONS SMT VERSION INSTALLATION ALARM PORT NUMBER 1 2 3 4 5 6 7...

Страница 7: ...the master port data rate for 9600 baud Master Port Protocol Switches S1 5 through S1 8 Unless system requirements dictate otherwise set the master port protocol to DCPF Port Termination SMT Version O...

Страница 8: ...S2 Not Used SWITCH S3 SMT VERSION ONLY PortTermination Port 1 Terminated Port 2 Terminated Port 3 Terminated Port 4 Terminated Port 5 Terminated Port 6 Terminated Port 7 Terminated Port 8 Terminated...

Страница 9: ...ble 12 VDC Output WRT 12 VDC Output Serial Output Data 5 VDC Output MAP Channel Address 0 MAP Channel Address 2 MAP Channel Address 3 TXD Modem Data Connection MAP Channel Address 1 21 to 56 VDC Alarm...

Страница 10: ...and other functions Four green LEDs labeled A B C and D have various func tions Refer to the documentation specific to the MAP firm ware One green LED labeled RX DATA indicates that the data ports are...

Страница 11: ...sion 21 VDC 24 VDC 48 VDC 56 VDC OutputVoltageandCurrent DATA RATES MasterPort Data Port PhysicalDimensions Weight OperatingTemperatureRange VALUE 21 to 56 VDC 300 mA 268 mA 155 mA 140 mA 133 mA 120 m...

Страница 12: ...en instrument signed by a duly authorized officer of the Seller and accepted by the Buyer Warranty and remedies on products not manufactured by the Seller are in accordance with warranty of the respec...

Отзывы: