INSTALLATION

I

nstallation consists of setting the straps and switches, wiring

the pin connectors, installing the module in the equipment

shelf, and checkout.

1. Set the straps and switches.

Refer to Fig. 3 and Table A. The SAM has a four mini-DIP
switches that select the time-out interval. If you don’t need that
time-out feature, do not set any switches in the ON position.

Straps determine whether the relays follow the inputs or the
latch.

F

IG

. 3 - S

WITCH

 

AND

 S

TRAP

 L

OCATIONS

, 46019 SAM

T

ABLE

 A - S

WITCH

 S

ETTINGS

, 46019 SAM

OPTION

Switch 1 ON, all others OFF
Switch 1 ON, all others OFF
Switch 1 ON, all others OFF
Switch 1 ON, all others OFF
All Switches set OFF

DESCRIPTION

Time Out After 0.5 Minutes
Time Out After 1.0 Minutes
Time Out After 4.0 Minutes
Time Out After 8.0 Minutes
No Time Out

NOTE:

 Set only one (1) switch ON at a time.

CONTINUED

 . . .

CIRCUIT "A"
CIRCUIT "B"
CIRCUIT "C"
CIRCUIT "D"

FOLLOW

LATCH

TIME

OUT

SWITCH

1234

OFF

ON

Содержание 46019

Страница 1: ...NWT 000870 Copyright 1998 by Dantel Inc Dantel is a registered trademark of Dantel Inc ISO 9001 Registered Printed in the U S A INSTALLATION OPERATION MANUAL 46019 0298 90 00028 46019 SUMMARY ALARM M...

Страница 2: ...nto any 400 type or similar equipment housing The SAM does not accept subassem blies The SAM operates on 21 to 56 VDC input power CIRCUIT DESCRIPTION Fig 1 shows the 46019 Summary Alarm Module functio...

Страница 3: ...nergizes that individual level relay s operating coil Each relay has two sets of relay contacts visual and audible Each set has normally open NO and normally closed NC contacts The common relay operat...

Страница 4: ...45 56 VISUAL CONTACTS AUDIBLE CONTACTS OUTPUT RELAYS N O COMM N C BATT 10K OFF 54 24 VISUAL CONTACTS AUDIBLE CONTACTS COMMON RELAY COMM BATT SWITCH TIME SELECTOR Set only one switch on 0 5 1 4 8 TTL O...

Страница 5: ...trolled by the SAM s relays on another floor for example the central office The external indicators on another floor act independently of the alarm shelf processor The alarm shelf processor reports to...

Страница 6: ...hes in the ON position Straps determine whether the relays follow the inputs or the latch FIG 3 SWITCH AND STRAP LOCATIONS 46019 SAM TABLE A SWITCH SETTINGS 46019 SAM OPTION Switch 1 ON all others OFF...

Страница 7: ...evel A TTL Input Level A Visual Relay Common Level A Visual Relay N C Level A Visual Relay N O Level A Optically Coupled Input Level B TTL Input 21 to 56 VDC Input Level B Optically Coupled Input Leve...

Страница 8: ...part operation of the 46019 Summary Alarm Module consists of observing the LEDs or operating one of the front panel Alarm Cut Off ACO switches Interrupt alarm signaling by moving the appropriate fron...

Страница 9: ...owledge In Optically Coupled Normal Acknowledged TTL Normal Acknowledged Common External Acknowledge Input To Operate Relay Contact Rating 30 VDC 125 VAC Physical Dimensions Weight Operating Temperatu...

Страница 10: ...n instrument signed by a duly authorized officer of the Seller and accepted by the Buyer Warranty and remedies on products not manufactured by the Seller are in accordance with warranty of the respect...

Отзывы: