NOTE: This section lists the different options available for this product. To order any of the avail-

able options, contact Dantel Inside Sales through our toll-free number, 1-800-432-6835.

OPTION NUMBER

FEATURES

A11-46017-01

Summary Audible Alarm Module (SAAM)

A11-46017-11

Summary Audible Alarm Module (SAAM)

ORDERING INFORMATION

T

he 46017 Summary Audible Alarm Module (SAAM) provides

a highly recognizable two-level audio alarm indicator and

alarm status display to alert service personnel of an alarm. The
module is part of Dantel’s 460 Alarm and Control System.

The 46017 SAAM indicates alarms audibly and visually, re-
motely or locally. It accepts 16 external alarms, summed in two
groups of eight. Each group of eight alarms reports with a
different tone rate, allowing priority alarms to be grouped
together and audibly recognized.

The 46017 SAAM also provides relays to control external audio
and visual alarm indicating devices.

A timer can be set to acknowledge all alarms automatically.

There are two options of the module:

46017-01 - The first four inputs of each group are TTL as well as
optically coupled (OC) inputs. The second four inputs of each
alarm group are OC only.

46017-11 - The same as the 46017-01 except that inputs 5
through 8 of Alarm Group 1 and inputs 13 through 16 of Alarm
Group 2 are TTL inputs instead of OC inputs.

The 46017 SAAM is a plug-in printed circuit module that fits
into any Dantel 400-type or similar equipment housing. It
operates on -21 to -56 VDC input power.

The front panel includes:

Two status-indicating LEDs for each alarm input

A Sonalert audible alarm with Alarm Cut-Off (ACO) switch
and LED

Alarm acknowledge buttons for each alarm group

Alarm Cut-Off (ACO) switches

LEDs for external alarm indicating devices for each alarm
group

An external Alarm Acknowledge button

GENERAL DESCRIPTION

Содержание 46017

Страница 1: ...fer to BellcoreTM Technical Reference TR NWT 000870 Copyright 1998 by Dantel Inc Dantel is a registered trademark of Dantel Inc ISO 9001 Registered Printed in the U S A INSTALLATION OPERATION MANUAL 4...

Страница 2: ...ogether and audibly recognized The 46017 SAAM also provides relays to control external audio and visual alarm indicating devices A timer can be set to acknowledge all alarms automatically There are tw...

Страница 3: ...button will acknowledge alarms on the 46017 SAAM and all modules to which the switch is wired Set the DIP switches to acknowledge alarms automatically after a certain time out period refer to Table A...

Страница 4: ...E 4 46017 0398 90 00006 FIG 1 FUNCTIONAL SCHEMATIC 46017 K4 K3 AUTOMATIC ALARM ACKNOWLEDGEMENT CIRCUIT TTL OC TTL OC TTL OC TTL OC OC OC OC OC TTL OC TTL OC TTL OC TTL OC OC OC OC OC CIRCUIT DESCRIPTI...

Страница 5: ...alarms will reactivate the relays and audible alarm and restart the timer When the time out function is not used the relays and audible alarm remain active until you acknowledge the alarms Audio Driv...

Страница 6: ...provides a different audio and or visual signal Two groups use the 46017 SAMM on board Sonalert The other two control an external audio or visual device with their alarm enabled relays K1 B pins 56 an...

Страница 7: ...pplication can use up to 16 MATs Level A outputs with the greatest priority should connect to Group 2 because that group always precedes Group 1 FIG 3 SINGLE LEVEL ALARM REPORTING APPLICATION ALARM OU...

Страница 8: ...group TTL inputs for in shelf applications only FIG 4 SINGLE LEVEL OR MULTIPLE LEVEL ALARM REPORTING APPLICATION 46017 SUMMARY AUDIBLE ALARM MODULE 46020 MULTIPLE ALARM PROCESSOR DATA PORT Subassembl...

Страница 9: ...losed NEW relay contact does not signal the external device If the NEW relay drops the EXIST relay does not signal the external device The built in audible device continues operating until it times ou...

Страница 10: ...LEDs and releases the NEW relays After the time out period any new alarms will reactivate the relays and audible alarm and restart the timer When the time out func tion is not used the relays and audi...

Страница 11: ...re the relays to external audio and visual alarm indicating devices One method is shown in Fig 7 where external devices follow the alarms or acknowledgment by chaining the EXIST and NEW relays togethe...

Страница 12: ...OR Closed K2 B NOR Open K2 A NOR Open K2 B Common Group 1 Acknowledge In K2 A NOR Closed Circuit 2 TTL Input K2 A Common Circuit 4 TTL Input Circuit 3 TTL Input 21 to 56 VDC Circuit 1 TTL Input Circui...

Страница 13: ...ates which of the 16 alarm inputs has an alarm present The lower row of LEDs in each alarm group NEW indi cates an alarm that has not been acknowledged You can acknowledge alarms in one of several way...

Страница 14: ...125 VAC Alarm Input Requirements TTL Inputs Optically Coupled Inputs Audio Alarm Type and Frequency Temperature Range Physical Dimensions Weight VALUE 21 to 45 VDC 50 mA 40 mA 250 mA 280 mA 3 6 Btu Hr...

Страница 15: ...46017 0398 90 00006 PAGE 15 NOTES...

Страница 16: ...n instrument signed by a duly authorized officer of the Seller and accepted by the Buyer Warranty and remedies on products not manufactured by the Seller are in accordance with warranty of the respect...

Отзывы: