Installation procedure

1. Please read these notes carefully before commencing work. In case of 

doubt please consult a qualified electrician.

2. POSITIONING: The CESPLL10VDC (IP66) should be installed to 

achieve correct coverage of the area, see diagram B. Avoid locating this 

product where it is exposed to drafty conditions (exposed lobbies, open 

ceiling voids or near fans) or near heat sources.

3.  To cover larger areas and corridors PIRs should be spaced in a 5 metre grid 

formation, with one CESPLL10VDC(IP66) and the rest with switching PIRs 

with Volt Free secondary output and Normally Closed, Logic Gold relay 

contacts (CESFPIRVFNCLG) with all  

Switch Line outputs wired in series  

(diagram E). 

4. Make sure the power is  

isolated from the circuit.  

The PIR should be connected  

as shown in diagram C: 

 

Start-up mode

When the PIR is powered up, it will switch on the load for 1 minute, the load 

will then switch off and the PIR will enter its Operating Mode. If a manual 

override-off switch is positioned before the PIR in the circuit (diagram C, 

note 1) it will do this each time the wall switch is switched on.

 

Time, Lux and ‘Step Down’  set-up

For convenience, ensure that the TIME is set to the minimum when setting up 

the LUX level. Afterwards set the TIME to a value suitable for the application.
The LUX is best set up when the local ambient light is at approximately  the 

minimum desired working light level. With the LUX set fully clockwise wait 

for the PIR to switch off. Rotate the LUX adjuster slowly anticlockwise (- to 

+), whilst waving your hand approximately 1m below the PIR, until the load 

switches on.

The single adjuster spindle on the back of the PIR is used to regulate the ‘Step 

Down’ illuminance function lux level, see diagram A opposite. This must be 

adjusted in situ so that the desired level of brightness is achieved under the 

luminaire(s) being controlled. In areas where no natural daylight is present it 

is advised that the LUX level is set to

 ͚

.  inhibit off.

L

N

       1

    t

s

a

ll

a

b

       10

       1

    t

s

a

ll

a

b

       10

       1

    t

s

a

ll

a

b

       10

CESPLL10VDC (IP66)

control lines

230 VAC

Optional 

switch for 

overriding off

TIME

min

max

LUX

max

min

SENS

min

max

20s

40s

1m15s

2m30s

5m

10m

10s

20m

40m

100

1000

66%

100%

Typical settings

up to 5m
up to 7m

Strong detection zone 

i.e. person moving arm

or walking towards PIR

Secondary detection zone

i.e. person walking

perpendicular to PIR 

For optimum coverage

recommended mounting

height: 2.4 to 5m

B: Detection diagram

C:  Wiring diagram, 

single PIR

D:  Adjusting time 

and lux at the 

side of product

‘Step Down’ set-up

The  STEP  DOWN  low  light  level  range  is 

adjusted via the spindle on the top of the product 

and allows the 1-10VDC ballast to switch from 

10% to 100% in 9 steps. Fully clockwise will allow 

the ballast to switch to 100% on nonoccupation. 

Fully anti-clockwise will allow the ballast to 

switch to 10% on non-occupation.

A: ‘Step Down’ adjuster on   

      the back of the product

100%

10%

L

Step 

Down 

Adjuster

Terminal 

block