DANLERS CEFL PIR LR Скачать руководство пользователя страница 1

DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.

Telephone: +44 (0)1249 443377   Fax: +44 (0)1249 443388   

E-mail: [email protected]    Web: 

www.danlers.co.uk

Company Registered Number 2570169   VAT Registration Number 543 5491 38

Also available from DANLERS

•  PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers 
•  Photocells  •  Radio  remote  controls  • Time  lag  switches  •  Outdoor  security  switches 
•  Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products

Please call for more information or a free catalogue, or visit our website.

This product conforms to BS EN 60669-2-1.
Please ensure the most recent edition of the appropriate local wiring regulations are observed 
and suitable protection is provided e.g. 6 amps over current, 1kV over voltage. Please ensure 
that this device is disconnected from the supply if an insulation test is made. 
This product is covered by a warranty which extends to 5 years from the date of manufacture.

Precautions and Warranty 

Installation notes

  Ceiling Long Range PIR occupancy switch 

 

CEFL PIR LR

DANLERS  ceiling  long  range  PIR  occupancy  switches  are  mains 
powered (230Vac) and can be mounted into the ceiling void through a 
ceiling board or within a lighting luminaire (diagram A). They incorporate 

a 2 meter connecting flex to make installation quicker and easier.

They incorporate a passive infra-red quad sensor to detect movement 
of a warm body within their detection zone (diagram B) and a photocell 
to monitor the ambient light level.
On detecting movement, if the ambient light level is not above an ambient 
threshold, the PIR will switch the load on. The ambient threshold can 

be set by the user to between approximately 100 lux and infinite lux 

(photocell inactive) via the LUX adjuster (diagram C).
If no more movement is detected within a certain time, then the PIR 
will switch off the load. The time can be set via the TIME adjuster to 
10 seconds, 20s, 40s, 1 minute 15s, 2m30s, 5m, 10m, 20m or 40 
minutes (diagram E).

Loading limits

DANLERS CEFL PIR LR units can switch up to 6 amps (1500W) of: 

•  Fluorescent lamps, either high frequency of switch start 
•  Incandescent or mains halogen lamps

 (recommended with integral safety fuse) 

•  Electronic or wire wound transformers.

They can also switch up to: 

•  2 amps (500W) of compact fluorescent or LED lamps (typically 50 lamps)

 

•  1 amp (250W) of Fans.

21/01/11

INS943 CEFL PIR LR

Variants

As DANLERS design and manufacture in the UK, variants can be supplied, 

coded by the following suffixes, applied in this order:

•  12V or 24V   

12V and 24V (ac or dc) operation 

•  VF 

 

 

Volt Free contacts 

•  GOLD or LG 

Gold or Logic Gold contacts 

•  NC 

 

 

Normally Closed contacts 

•  3M 

 

 

3 Metre (or other) length flex

The details of these variants are covered by an enclosed addendum 

installation note if applicable.

Fault finding

 

The load will not switch on: 

•  The LUX adjuster is set too low and is inhibiting the switch. 

•  The moving body is not emitting more IR than the background. 

    (Person wearing insulating clothing in a warm environment) 

•  Person is too far from the PIR switch, see detection diagrams. 

•  Person is moving unusually slowly (perhaps when testing). 

The load switches on when nobody is present: 

•  Heating source causing IR variations 

•  Direct light pollution causing IR variations 

•  Ceiling void drafts or fans causing excessive air movement. 

Отзывы: