Installation notes

DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.

Telephone: +44 (0)1249 443377   Fax: +44 (0)1249 443388   

E-mail: [email protected]    Web: www.danlers.co.uk

Company Registered Number 2570169   VAT Registration Number 543 5491 38

Products available from DANLERS

•  PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers 

•  Photocells • Radio remote controls • Time lag switches • Outdoor security switches 

•  Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products

Please call for more information or a free catalogue.

This product conforms to BS EN 60669-2-1.
Please ensure the most recent edition of the appropriate local wiring regulations are observed 

and suitable protection is provided e.g. over current protection, 1kV over voltage. Please ensure 

that this device is disconnected from the supply if an insulation test is made. 
This product is covered by a warranty which extends to 5 years from the date of manufacture.

Precautions and Warranty 

  Batten Mount PIR occupancy switches
 

BMPIR5M      BMPIR10M      BMPIRSP      BMPIRRH

DANLERS Batten mount passive infra-red occupancy switches (PIR) 

can be mounted onto the end of lighting battens via the 20mm knock 

out. The switch includes the connection 20mm thread and 1m of wire  

tails to connect to the lighting ballast.

The  PIRs  incorporate  a  passive  infra-red  quad  sensor  to  detect 

movement of a warm body within the detection zone and include a 

photocell to monitor the ambient light level. 
On detecting movement, if the ambient light is dark enough, the PIR 

will switch the load on. The ambient threshold can be set by the user 

to between approximately 100 and 3000 lux (on the working plane) 

via the LUX adjuster.  
BMPIR5M has a 5m diameter range, 5m max height, see diag. B.

 

BMPIR10M has a 10m diameter range, 5m max height, see diag. B.

 

BMPIRSP has a 1.5m diameter range, 5m max height, see diag. B.

 

BMPIRRH has a 2.5m diameter range, 2.5m max height, see diag. B.

A ‘real time’ photocell status indicator glows green when the photocell 

is active and glows red when the photocell is inactive.
If no more movement is detected within a certain time, then the PIR will 

switch off the load. The time can be set via the internal TIME adjuster 

to between 10seconds and 40 minutes (diagram D).

Loading

These PIRs should only be connected to a 230V 50Hz ac supply. 

They can switch the following type of loads:
•  10 amps (2500W) resistive loads and tungsten 
•  6 amps (1500W) fluorescent (switch start) / mains halogen lamps 

 

  (recommended with integral safety fuse)
•  3 amps (750W) electronic or wire wound transformers.

 

•  2 amps (500W) CFL, 2D lamps, LED Drivers and LED lamps 

 

  and fittings.
Normally OPEN contacts.

13/03/15

INS713 BMPIR5M / 10M / SP / RH

Wiring diagram

 

 
The PIR does not detect 

•  Person is too far from the PIR switch, see detection diagram.

 

•  Person is moving unusually slowly (perhaps when testing).

The PIR false triggers

 

•  Detector is placed too close to heat or moving air sources. 

 

Trouble shooting

load

optional manual 

wall switch for  

overriding off 

230 VAC

SL

N

L

load

optional manual 

wall switch for 

overriding off

N

230 VAC

SL

N

SL

N

Single BMPIRxx

A few BMPIRxx wired in parallel

BMPIR5M/10M/SP/RH