MODEL 2234 DIGITAL FLOW COMPUTER ___________________________
Table 2-5. Error Code Diagnostic Chart
(Continued)
Error Code
Possible Cause
Check
Solution
31
five volt
calibration
error
1. Possibly 24 volt
circuit is out of
tolerance.
1. Check voltage on
PC Board 1 with a
digital voltmeter for
5.000 volt.
Check command code
99 for FIC.
1. Adjust 24-volt
supply output for
5.000 volts per
paragraph 4.2.4.
2. Perform reference
and rate voltage
calibrations per
paragraphs 4.3.1 and
4.3.2.
SECTION 2
63
Содержание 2234
Страница 2: ......
Страница 23: ...MODEL 2234 DIGITAL FLOW COMPUTER ___________________________ Figure 1 1 Model 2234 Display SECTION 1 11 ...
Страница 28: ...__________________________ MODEL 2234 DIGITAL FLOW COMPUTER This page intentionally left blank SECTION 1 16 ...
Страница 37: ...MODEL 2234 DIGITAL FLOW COMPUTER ___________________________ Figure 2 2 Model 2234 Keyboard SECTION 2 25 ...
Страница 76: ...__________________________ MODEL 2234 DIGITAL FLOW COMPUTER This page intentionally left blank SECTION 2 64 ...
Страница 156: ...__________________________ MODEL 2234 DIGITAL FLOW COMPUTER Figure 4 4 PC Board No 2 Adjustment Locations SECTION 4 144 ...
Страница 170: ...__________________________ MODEL 2234 DIGITAL FLOW COMPUTER This page intentionally left blank APPENDIX A 158 ...
Страница 172: ...__________________________ MODEL 2234 DIGITAL FLOW COMPUTER This page intentionally left blank APPENDIX B 160 ...
Страница 173: ......
Страница 174: ......
Страница 175: ......
Страница 176: ......
Страница 177: ......
Страница 178: ......
Страница 179: ......
Страница 180: ......
Страница 182: ......
Страница 184: ......
Страница 185: ......