EMC tests
EMC tests
Value
Electrostatic discharge immunity test (EN61000-4-2)
6 kV Contact discharge 8 kV Air
discharge
Electrostatic discharge immunity test (ISO10605:2008)
Operation:8 kV contact and 15 kV
air discharge Handling: 8 kV
contact and air discharge
Electromagnetic field immunity test (EN61000-4-3)
10 V/m (80 - 1000 MHz) 3 V/m (1.4 -
2.7 GHz)
Electrical fast transient/burst immunity test (EN61000-4-4)
Supply Line: 2 kV Signal Line: 1 kV
Surge immunity test (EN61000-4-5)
Supply Line: 0.5 kV
Induced disturbances immunity test (EN61000-4-6)
10 V
Magnetic field immunity test (EN61000-4-8)
30 A/m
Conducted Emissions (CISPR 16-2)
Class B
Radiated Emissions (CISPR 16-2)
Class B
Electromagnetic field immunity test (ISO11452-4)
60mA (20 - 80 MHz) 30 V/m (80 -
1000 MHz)
Electrical transient immunity test on supply lines (ISO7637-2)
Test pulse 1, 2a/b, 3a/b, 4, 5a
Conducted Transient Emissions (ISO 7637-2)
Radiated Emissions (CISPR 25)
FCC Part 15/47 CFR Ch. I
Class B
Electrical loads
Electrical loads
Value
ISO 16750-2 (Code AE. Level IV)
Temperature / climate tests
Temperature / climate tests
Value
Temperature cycle EN 60068-2-14 Nb: 2010-04
-30 °C … +75 °C
10 cycles
Temperature shock EN 60068-2-14 Na: 2010-04
-40 °C … +85 °C
10 cycles
Damp heat, cyclic EN 60068-2-30 Db: 2006-06
+55 °C, 95% rH
2 cycles
Technical Information
WS 403 Remote Solution
Tests