Single compressors
Electrical data, connections and wiring
Compressor electrical
specifications
Compressor rated
voltage (V)
Model
RW(Ω) at 20°C line
to line
RLA (A)
Max Operating
Current (A)
414 V max.
VZH044CG
0.708±7%
15.5
17.8
VZH035CG
12.4
14.3
VZH028CG
10.3
11.8
177 V max.
VZH044CJ
0.185±7%
33.3
38.3
VZH035CJ
26.6
30.6
VZH028CJ
22.0
25.3
RW: Winding resistance per winding, measured at motor terminals
RLA: Rated load Amp
Because VZH compressors are powered by a
frequency converter, the mains frequency, 50 or
60 Hz, is no longer an issue. Only the mains
voltage is to be taken into account. With 2 motor
voltage codes, the most common mains voltages
and frequencies are covered. Never connect the
VZH compressor directly to the mains power
supply in the case motor burns out.
Supply voltage
Voltage code
Mains voltage range of drive
J
200-240 V / 3 ph / 50 Hz &
200-240 V / 3 ph / 60 Hz (±10%)
G
380-480 V / 3 ph / 50 Hz &
380 - 480 V / 3 ph / 60 Hz (±10%)
Rated Load Amp value is the current value at
maximum load, in the operating envelope, and
at maximum speed and maximum drive input
voltage.
RLA (Rated Load Amp)
Max Operating Current (A)
Wiring connections
Max operating current is the maximum
continuous current which is 115% of RLA. This
value is printed on compressor nameplate.
VZH scroll compressors will only compress gas
while rotating counter-clockwise (when viewed
from the top of the compressor).
The drawing shows electrical terminal labeling
and should be used as a reference when wiring
the compressor.
U, V & W of the drive and the compressor must be
connected accordingly.
For use of EMC bracket with shielded cable, it is
recommended to have a thread cutting screw
(#10-32) having a torque of 3NM.
Earth grounding
EMC bracket to
terminations of
shielded wire
Terminal cover mounting
The terminal cover and gasket should be installed
prior to operation of the compressor. The terminal
cover has two outside tabs, 180 degrees apart,
that engage the terminal fence. When installing
the cover, check that it is not pinching the lead
wires.
Terminal cover removal
push
push
push
17
FRCC.PC.034.A2.02
Application Guidelines
Содержание VZH028
Страница 1: ...Inverter scroll compressors VZH028 035 044 single R410A Application guidelines http cc danfoss com...
Страница 2: ......
Страница 3: ...Content VZH028 035 044 single compressors 4 3 FRCC PC 034 A2 02 Application Guidelines...
Страница 43: ...Single compressors Trouble shooting 06 03 2015 page 5 43 FRCC PC 034 A2 02 Application Guidelines...