flow  and  pressure  drops  (solenoid  valve,  filter 

dryer, expansion valve, etc.), refrigerant charge.

  •   Low  refrigerant  charge:  The  correct  refrigerant 

charge is given by the liquid sight glass indication, 

the  condenser  delta T  in  relation  to  the  refrige-

rant  pressure  tables  (pressure-temperature),  the 

superheat and the sub-cooling, etc. (if additional 

charge is deemed necessary, refer to section 8).

  •   Compressor  short  cycling:  The  number  of 

cycles shall never exceed 12 starts per hour.

12 - Maintenance

  Internal  pressure  and  surface  temperature 

are dangerous and may cause permanent injury.

Maintenance  operators  and  installers  require 

appropriate  skills  and  tools.  Tubing  and  com-

presssor  upper  shell  temperature  may  exceed 

100°C and can cause severe burns.

  Ensure  that  periodic  service  inspections  to 

ensure system reliability and as required by local 

regulations are performed.

To prevent system related compressor problems, 

following periodic maintenance is recommended:

  •   Verify that safety devices are operational and 

properly set.

  •   Ensure that the system is leak tight.

  •   Check the compressor current draw.

  •   Confirm that the system is operating in a way 

consistent  with  previous  maintenance  re-

cords and ambient conditions.

  •   Check that all electrical connections are still 

adequately fastened.

  •   Keep the compressor clean and verify the ab-

sence of rust and oxidation on the compres-

sor shell, tubes and electrical connections.

  •   Check  the  internal  temperature  of  the  fre-

quency converter on its display and the coo-

ling  air flow.

  •   Faults are logged in the frequency converter 

memory and can be displayed. This can help 

to  evaluate  and  improve  parameters  of  the 

frequency converter or of the system itself.

13 - Warranty

Always  transmit  the  model  number  and  serial 

number  with  any  claim  filed  regarding  this  pro-

duct.

Use the fault memory of the frequency conver-

ter to recover the fault descriptions before ini-

tializing the system and even before shutting off 

the power.

The product warranty may be void in following 

cases:

  •   Absence of nameplate.

  •   External  modifications;  in  particular,  drilling, 

welding, broken feet and shock marks.

  •   Compressor opened or returned unsealed.

  •   Rust,  water  or  leak  detection  dye  inside  the 

compressor.

  •   Use of a refrigerant or lubricant not approved 

by Danfoss.

  •   Any  deviation  from  recommended  instruc-

tions pertaining to installation, application or 

maintenance.

  •   Use in mobile applications.

  •   Use in explosive atmospheric environment.

  •   No model number or serial number transmit-

ted with the warranty claim. 

14 – Disposal

Danfoss  recommends  that  compressors, 

frequency converters and compressor oil 

should be recycled by a suitable company.

Danfoss Commercial Compressors http://cc.danfoss.com

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products 

already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.

All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

FRCC.EI.024.A1.02 - October 2012 

Copyright Danfoss Commercial Compressors - 10/12

Instructions

Отзывы: