18 DKDHR 

VI.GP.P1.02 

Danfoss District Energy

Instructions 

 

 

 

VX Solo II

6.7 VX Solo II H2WP (ECL 210/A260.1d) - 2 HE c prim. connection for DHW cylinder

Plate heat exchanger

Differential pressure controller

Circulation pump, HE 

10  Circulation pump, FH 

16  Expansion vessel

24  Fitting piece for heat meter

25  Electronic controller 

29  Actuator AMV 13

30  Flow controller with integrated control valve AHQM

33  Actuator AMV 150

34  3-way valve VMV 30/15

57  Safety temperature monitor

 

 

The substations offer variable connection possibilities, as 

connection of pipes can be established both in the top or in 

the bottom of the substation.

Please note: 

Your substation may look different than the substation shown, as 

variants with other components may be supplied. The control func-

tion, however, is basically as stated in this instruction manual.

Instructions for the fitted components will be supplied together with 

the substation.

1

25

29

30

8

24

10

4

57

33

34

Measurements:

Dimensions without cover

H860 x W650 x D365 mm

Dimensions with cover

H860 x W700 x D380 mm

Connections:

Order:

District heating (DH) supply

District heating (DH) return

Heating (HE) return

Heating (HE) supply

Floor heating (FH) supply

Floor heating (FH) return

Cylinder supply

Cylinder return

Connection sizes:

DH + Cylinder:  G¾ (ET)

HE + FH: 

G¾ (IT)

Primary

Secundary

FH supply

FH r

etur

n

HE r

etur

n

HE supply

DH supply

DH r

etur

n

Cylinder supply

Cylinder r

etur

Secundary

Primary

16

top view

Wall

Содержание VX Solo II

Страница 1: ...er 18 6 8 VX Solo II H2WS ECL 310 A367 1d 2 HE circuits sec connection for DHW cylinder 19 6 9 VX Solo OP ECL 210 A237 1a 1 HE circuit sec connection for DHW cylinder 20 7 0 Mounting 21 7 1 Variable c...

Страница 2: ...ture The stations work at a maximum supply temperature from the district heating network of 110 C and the stations work with a op erating pressure of 16 bar which may put the user at risk of burns fro...

Страница 3: ...HE with insulation 4 Differential pressure controller AVPL 5 Strainer 7 Ball valve 8 Circulation pump HE 11 Safety valve HE 2 5 bar 13 Thermometer 14 Pocket for pressure gauge 15 Manometer 16 Expansi...

Страница 4: ...HE 11 Safety valve HE 13 Thermometer 14 Pocket for pressure gauge 15 Manometer 16 Expansion vessel 23 Sensor pocket for heat meter 24 Fitting piece for heat meter 3 4 x 110 mm 25 Controller Danfoss E...

Страница 5: ...14 Pocket for pressure gauge 15 Manometer 16 Expansion vessel 23 Sensor pocket for heat meter 24 Fitting piece for heat meter 3 4 x 110 mm 25 Controller Danfoss ECL 210 A260 1d 26 Outdoor sensor Danfo...

Страница 6: ...VPB F 5 Strainer 7 Ball valve 8 Circulation pump HE 11 Safety valve HE 13 Thermometer 14 Pocket for pressure gauge 15 Manometer 16 Expansion vessel 23 Sensor pocket for heat meter 24 Fitting piece for...

Страница 7: ...Cylinder 11 Safety valve HE 13 Thermometer 14 Pocket for pressure gauge 15 Manometer 16 Expansion vessel 23 Sensor pocket for heat meter 24 Fitting piece for heat meter 3 4 x 110 mm 25 Controller Danf...

Страница 8: ...ometer 14 Pocket for pressure gauge 15 Manometer 16 Expansion vessel 23 Sensor pocket for heat meter 24 Fitting piece for heat meter 3 4 x 110 mm 25 Controller Danfoss ECL 210 A247 1c 26 Outdoor senso...

Страница 9: ...ation pump FH 11 Safety valve HE 13 Thermometer 14 Pocket for pressure gauge 15 Manometer 16 Expansion vessel 23 Sensor pocket for heat meter 24 Fitting piece for heat meter 3 4 x 110 mm 25 Controller...

Страница 10: ...13 Thermometer 15 Manometer 16 Expansion vessel 23 Sensor pocket for heat meter 24 Fitting piece for heat meter 3 4 x 110 mm 25 Controller Danfoss ECL 310 A367 1d 26 Outdoor sensor Danfoss ESMT 27 Sen...

Страница 11: ...1 Safety valve HE 13 Thermometer 15 Manometer 17 Air valve 23 Sensor pocket for heat meter 24 Fitting piece for heat meter 3 4 x 110 mm 25 Controller Danfoss ECL 210 A237 1a 26 Outdoor sensor Danfoss...

Страница 12: ...station may look different than the substation shown as variants with other components may be supplied The control func tion however is basically as stated in this instruction manual Instructions for...

Страница 13: ...station Please note Your substation may look different than the substation shown as variants with other components may be supplied The control func tion however is basically as stated in this instruct...

Страница 14: ...the substation Please note Your substation may look different than the substation shown as variants with other components may be supplied The control func tion however is basically as stated in this...

Страница 15: ...Your substation may look different than the substation shown as variants with other components may be supplied The control func tion however is basically as stated in this instruction manual Instructi...

Страница 16: ...on Please note Your substation may look different than the substation shown as variants with other components may be supplied The control func tion however is basically as stated in this instruction m...

Страница 17: ...the bottom of the substation Please note Your substation may look different than the substation shown as variants with other components may be supplied The control func tion however is basically as st...

Страница 18: ...ation Please note Your substation may look different than the substation shown as variants with other components may be supplied The control func tion however is basically as stated in this instructio...

Страница 19: ...e substation Please note Your substation may look different than the substation shown as variants with other components may be supplied The control func tion however is basically as stated in this ins...

Страница 20: ...ion manual Instructions for the fitted components will be supplied together with the substation 1 25 29 30 Measurements Dimensions without cover H640 x W440 x D250 mm Dimensions with cover H640 x W500...

Страница 21: ...e dimensioning basis re tighten the connections and take the substation into continuous use Please note that the connections may be supplied with EPDM rub ber gaskets in general connection sizes from...

Страница 22: ...Mounting height approx 2 5 m above ground Temperature range 50 to 50 C Electrical connections Two wire non polarized can be crossed Sensor cable 2 x 0 4 1 5 mm Connect the cable ends to ECL controlle...

Страница 23: ...hut off valves are closed threaded and flanged connections are tightened Adding water to the system 1 Pump must be switched off when water is added to the system 2 Fill heat exchanger and system with...

Страница 24: ...controller settings can be changed in accordance with the en closed producer instructions Differential pressure controller PN 16 AVPL Return mounting adjustable setting Alternative differential press...

Страница 25: ...rature approx 65 C It is important to keep the supply temperature to the radiators as low as possible the temperature is indicated by thermometer mounted in HE return The room temperature is controlle...

Страница 26: ...mmer period The controller settings can be changed in accordance with the en closed producer instructions for the mounted controller See ECL Application Key Box with ECL Comfort 210 310 user guide and...

Страница 27: ...T www danfoss com Page 7 DANsK Flow og temperatur regulator med indbygget motorventil AVQM AVQMT www danfoss dk Side 9 DEUTsCh Volumenstrom und Temperatur Regler mit Motorstellventil AVQM AVQMT www da...

Страница 28: ...ummer period The controller settings can be changed in accordance with the en closed producer instructions for the mounted controller See ECL Application Key Box with ECL Comfort 210 310 user guide an...

Страница 29: ...e controller with integrated control valve AVQM AVQMT www danfoss com Page 7 DANsK Flow og temperatur regulator med indbygget motorventil AVQM AVQMT www danfoss dk Side 9 DEUTsCh Volumenstrom und Temp...

Страница 30: ...trict Energy Instructions VX Solo II H2 ECL 210 260 Safety temperature monitor The floor heating circuit can be supplied with a safety thermostat for protection against overheating Please see enclosed...

Страница 31: ...the en closed producer instructions for the mounted controller See ECL Application Key Box with ECL Comfort 210 310 user guide and mounting guide for further information We also refer to Danfoss Insta...

Страница 32: ...punkts styring AMV 150 www danfoss dk Side 3 DEUTsCh Stellantriebe f r 3 Pkt Eingangssignal AMV 150 www danfoss de Seite 3 sVENsKA Motor f r 3 punktsreglering AMV 150 varme danfoss se Sida 4 NEDERlAND...

Страница 33: ...ump heating circuit See chapter 12 on page 48 for more information about circulation pump Domestic hot water TheVX Solo II HWP ECL 210 230 substations are supplied with con nection pipes for domestic...

Страница 34: ...roller settings can be changed in accordance with the en closed producer instructions for the mounted controller See ECL Application Key Box with ECL Comfort 210 310 user guide and mounting guide for...

Страница 35: ...VQM PN 25 AVQMT PN 25 AVQMT AVT PN 25 ENglIsh Flow and temperature controller with integrated control valve AVQM AVQMT www danfoss com Page 7 DANsK Flow og temperatur regulator med indbygget motorvent...

Страница 36: ...st possible speed of rotation setting 1 in due consideration of the electricity consump tion and the heating comfort Factory setting of the selector switch is centre position default Select setting 2...

Страница 37: ...settings can be changed in accordance with the en closed producer instructions for the mounted controller See ECL Application Key Box with ECL Comfort 210 310 user guide and mounting guide for further...

Страница 38: ...lventil AVQM AVQMT www danfoss de Seite 11 EsPA Ol Regulador de caudal y temperatura con v lvula de control integrada AVQM AVQMT www danfoss es P gina 13 slOVEN INA Regulator pretoka in temperature z...

Страница 39: ...pump It is recommended to set the pump at highest speed of rotation set ting 3 before start up Then set the pump at lowest possible speed of rotation setting 1 in due consideration of the electricity...

Страница 40: ...ler settings can be changed in accordance with the en closed producer instructions for the mounted controller See ECL Application Key Box with ECL Comfort 210 310 user guide and mounting guide for fur...

Страница 41: ...oss 01 2008 1 ENglIsh Actuators for three point control AMV 150 www danfoss com Page 2 DANsK Motorer til 3 punkts styring AMV 150 www danfoss dk Side 3 DEUTsCh Stellantriebe f r 3 Pkt Eingangssignal A...

Страница 42: ...supplied with a safety thermostat for protection against overheating Please see enclosed operating instructions Jumo AT Domestic hot water The VX Solo II H2WS ECL 310 A367 substations are supplied wi...

Страница 43: ...ller settings can be changed in accordance with the en closed producer instructions for the mounted controller See ECL Application Key Box with ECL Comfort 210 310 user guide and mounting guide for fu...

Страница 44: ...emperature controller with integrated control valve AVQM AVQMT www danfoss com Page 7 DANsK Flow og temperatur regulator med indbygget motorventil AVQM AVQMT www danfoss dk Side 9 DEUTsCh Volumenstrom...

Страница 45: ...erature in the cylinder is controlled by the Danfoss ECL controller Domestic hot water circulation pump It is recommended to set the pump at highest speed of rotation set ting 3 before start up Then s...

Страница 46: ...er settings can be changed in accordance with the en closed producer instructions for the mounted controller See ECL Application Key Box with ECL Comfort 210 310 user guide and mounting guide for furt...

Страница 47: ...ant for hating only See photo to the right Manual override AVQM Press and hold the button on the bottom side of the actuator during manual override Instructions AVQM AVQMT PN 16 25 DN 15 50 73695050 D...

Страница 48: ...ings which can be select ed with the push button Enclosed photo shows the recommended and alternative pump set tings for system types For further information about pump settings please refer to the en...

Страница 49: ...according to the enclosed instructions ALPHA2 GRUNDFOS INSTRUCTIONS Summer operation SubstationwithT Cthermostat In periods without heating demand the pump can be switched of on the switch and the shu...

Страница 50: ...easures after maintenance work After maintenance work and before switching the system on again Check that all screwed connections are tight Checkthatallsafetyfeatures covers thatwereremoved havebeen r...

Страница 51: ...ce sensor Defektive actuator Check the functioning of the actuator Defective motor valve or possibly dirt in the valve housing Check the functions of the motor valve clean valve housing if required Au...

Страница 52: ...ooling Strainer clogged Clean strainer Too small heating surface too small radiators compared to the total heating requirement of the building Increase total heating surface Poor utilization of existi...

Страница 53: ...g of the cylinder You may check the specifications of the manufacturer conc cylinder capacity Not enough pressure on the hot water Strainer in cold water meter clogged Clean strainer possibly in consu...

Страница 54: ...ntrols wrongly set Check that the controller has been cor rectly set see separate instructions Immersion sensor placed incorrectly Place immersion sensor correctly in ac cordance with the manufacturer...

Страница 55: ...ric standard Immunity for residential commercial and light industry EN 61000 6 2 2007 Electromagnetic compatibility Generic standard Immunity industry EN 61000 6 3 2007 Electromagnetic compatibility G...

Страница 56: ...Produced by Danfoss Redan A S 09 2011 Danfoss Redan A S Omega 7 S ften DK 8382 Hinnerup Phone 45 87 43 89 43 Fax 45 87 43 89 44 redan danfoss com www redan danfoss dk...

Отзывы: