Electrical Power Wiring
When tightening all electrical connections, it
is very important to tighten with the correct
torque. Too low or too high torque results in a
bad electrical connection. Always use a torque
wrench to tighten the bolts.
Connection Tightening
Torques
Table 33
Tightening Torques,
Drive Module
Table 34
Tightening Torques,
Motor Terminals
Type
Torque Nm (ft. lb.)
Phase
30 (22)
Grounding
20 (15)
Terminal No
Function
Torque [Nm (ft. lb.)]
Bolt Size
N165
Mains AC Input
Motor Output
High Voltage DC
(Regen)
Nominal: 29.5 (22)
Range: 19-40
(14-30)
M10
Earth (ground)
Nominal: 14.5 (11)
Range: 8.5-20.5 (8.5-15)
M8
N232 and N262
Mains AC Input
Motor Output
High Voltage DC
(Regen)
Earth (ground)
Nominal: 29.5 (22)
Range: 19-40
(14-30)
M10