6 Appendix
When assembling soft starter components, each bolt should
be tightened using a calibrated torque driver set to the
appropriate assembly torque. The following tables indicate
the different types of bolts and bolt tightening torques for
each assembly.
6.1.1 Input/Output Busbars to SCRs
Model
Bolt size
Torque (Nm)
MCD5-0021B
M5x12
4
MCD5-0037B
MCD5-0043B
MCD5-0053B
MCD5-0068B
MCD5-0084B
MCD5-0089B
MCD5-0105B
MCD5-0131B
M6x16
4
MCD5-0141B
M8x20
8
MCD5-0195B
MCD5-0215B
MCD5-0245C
MCD5-0360C
M8x16
12
MCD5-0380C
MCD5-0428C
MCD5-0595C
MCD5-0619C
MCD5-0790C
MCD5-0927C
MCD5-1200C
M10x35
20
MCD5-1410C
MCD5-1600C