0-81 Working Days
Array with 7 elements [0] - [6] displayed below parameter
number in display. Press OK and step between elements by
means of
▲
and
▼
buttons on the LCP.
Option: Function:
Set for each weekday if it is a working day or a non-
working day. First element of the array is Monday. The
working days are used for Timed Actions.
[0]
*
No
[1]
Yes
0-82 Additional Working Days
Array with 5 elements [0] - [4] displayed below parameter
number in display. Press OK and step between elements by
means of
▲
and
▼
buttons on the LCP.
Range:
Function:
Size related
*
[ 0 - 0 ]
Defines dates for additional
working days that normally
would be non-working days
according to
.
0-83 Additional Non-Working Days
Array with 15 elements [0] - [14] displayed below parameter
number in display. Press OK and step between elements by
means of
▲
and
▼
buttons on the LCP.
Range:
Function:
Size related
*
[ 0 - 0 ]
Defines dates for additional
working days that normally
would be non-working days
according to
0-89 Date and Time Readout
Range:
Function:
0
*
[0 - 0 ] Displays the current date and time. The date and
time is updated continuously.
The clock will not begin counting until a setting
different from default has been made in
.
Parameter Description