23-11 Maintenance Action
Option:
Function:
Select the action to be associated with
the Preventive Maintenance Event.
[1]
Lubricate
[2]
Clean
[3]
Replace
[4]
Inspect/Check
[5]
Overhaul
[6]
Renew
[7]
Check
[20] Maintenance Text 0
[21] Maintenance Text 1
[22] Maintenance Text 2
[23] Maintenance Text 3
[24] Maintenance Text 4
[25] Maintenance Text 5
23-12 Maintenance Time Base
Option:
Function:
Select the time base to be associated with the
Preventive Maintenance Event.
[0] Disabled
Disabled
[0] must be used when disabling the
Preventive Maintenance Event.
[1] Running
Hours
Running Hours
[1] is the number of hours the
motor has been running. Running hours are
not reset at power-on. The
Maintenance Time
Interval
must be specified in
.
[2] Operating
Hours
Operating Hours
[2] is the number of hours the
frequency converter has been running.
Operating hours are not reset at power-on.
The
Maintenance Time Interval
must be
specified in
23-13 Maintenance Time Interval
[3] Date & Time
Date & Time
[3] uses the internal clock. The
date and time of the next maintenance
occurrence must be specified in
23-14 Maintenance Date and Time
.
23-13 Maintenance Time Interval
Range:
Function:
1
h
*
[1 -
2147483647
h]
Set the interval associated with the current
Preventive Maintenance Event. This
parameter is only used if
Running Hours
[1]
or
Operating Hours
[2] is selected in
. The timer is
reset from
.
Example:
A Preventive Maintenance Event is set up
Monday at 8:00.
is
Operating hours
[2] and
23-13 Maintenance Time Interval
is 7 x 24
hours=168 hours. Next Maintenance Event
23-13 Maintenance Time Interval
Range:
Function:
will be indicated the following Monday at
8:00. If this Maintenance Event is not reset
until Tuesday at 9:00, the next occurrence
will be the following Tuesday at 9:00.
23-14 Maintenance Date and Time
Range:
Function:
Size
related
*
[ 0 -
0 ]
Set the date and time for next maintenance
occurrence if the Preventive Maintenance
Event is based on date/time. Date format
depends on the setting in
while the time format depends on the setting
in
.
NOTE
The frequency converter has no back up
of the clock function and the set date/
time will reset to default (2000-01-01
00:00) after a power down. In
it is possible to program for a
Warning in case the clock has not been
set properly, e.g. after a power down.
The time set must be at least one hour
from the actual time!
NOTE
When mounting an Analog I/O MCB 109
option card, a battery back up of the
date and time is included.
23-15 Reset Maintenance Word
Option:
Function:
Set this parameter to
Do reset
[1] to reset the
Maintenance Word in
and reset the message displayed in the LCP.
This parameter will change back to
Do not
reset
[0] when pressing OK.
[0]
*
Do not
reset
[1]
Do reset
NOTE
When messages are reset - Maintenance Item, Action and
Maintenance Date/Time are not cancelled.
is set to Disabled [0].