![Danfoss VLT PTC Thermistor Card MCB 112 Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/danfoss/vlt-ptc-thermistor-card-mcb-112/vlt-ptc-thermistor-card-mcb-112_operating-manual_3891319014.webp)
3.
-
Fit the MCB 112 in slot B, see
e
1
3
0
b
e
1
1
8
.1
1
A
B
D
Illustration 3: LCP Frame and Terminal Cover Removal
3.3 Sensor Circuit Wire Requirements
W A R N I N G
NO SAFE FUNCTION
Using sensor wires with a resistance >20 Ω causes the safe function not to work.
To ensure a properly working safe function, only use sensor circuit wires with a resistance <20 Ω.
Wire cross-section [mm
2
(AWG)]
Wire length [m (ft)]
1.5 (16)
2x800 (2x2625)
1 (17)
2x500 (2x1640)
0.75 (18)
2x300 (2x984)
0.5 (20)
2x250 (2x820)
AQ267038105120en-000101 / 130R0104
14 | Danfoss A/S © 2022.08
Installation
VLT® PTC Thermistor Card MCB 112
Operating Guide